Life Safety Q&A: Fire-rated door assemblies

By Brad Keyes / Special to Healthcare Facilities Today
September 13, 2017

Q: You have stated in previous Q&As that all fire-rated door assemblies must be tested and inspected. I don’t think that is true on fire-rated door assemblies that are not located in a fire-rated barrier. I was under the impression that the hospital’s current Life Safety drawings would be the determining factor on what barriers the hospital was responsible for maintaining. For example, if the building had rated doors on a wall that was not denoted as a fire rated barrier on the LS drawings, one could justify why there were not maintained. I run into the installation of unnecessary rated doors in many facilities, both old and new.

A: You make an interesting case. However, the Life Safety Code always trumps everything else, and in this case it would trump the hospital’s LS drawings. According to 7.2.1.15.2 of the 2012 LSC, it clearly says all fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80. There is no exception for fire-rated door assemblies that are not located in a fire-rated barrier.

My advice is to remove the fire-rated label if the facility is sure the barrier is not a fire-rated barrier.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 

See the latest posts on our homepage


Share

Topic Area: Regulations, Codes & Standards


Recent Posts
Recent Posts

48 hours after fire at Pa. senior facility, some residents were still missing


Residents were evacuated into bitter cold, and 27 were transported to hospitals

11/22/2017

Indiana hospital adopts recycling program for clean waste


Surgery generates about one-fourth of all hospital waste

11/22/2017

Focus: Facility Design

How healthcare facility design can improve patient well-being


Exposure to daylight as well as acoustical and thermal comfort are key

11/22/2017

Focus: Facility Design

Hennepin County Medical Center’s new ambulatory clinic building reaching for LEED Silver


The building will include six floors of clinics and services, two levels of underground pay parking with 221 stalls for patients and family

11/22/2017

Focus: Fire-Life Safety / Column

Life Safety Q&A: Exiting from hospital into medical building


Brad Keyes discusses exiting from a hospital into a medical building

11/22/2017





Post Comment




FREE
NEWSLETTER

• News and Updates
• Webcast Alerts
• Building Technologies



All fields are required.