Life Safety Q&A: Four-inch corridor projection

By Brad Keyes / Special to Healthcare Facilities Today
August 2, 2017

Q: With the adoption of the new 2012 Life Safety Code by CMS, we had a discussion about projections from the corridor wall. Since the LSC only allows projections to be 4 inches, the question that came up was in regards to fire extinguishers mounted to the wall and not recessed as they project out from the wall about 7 inches. Will we be required to recess them or will they be allowed? The same question was raised about wall mounted telephones?

A: Actually, the 2012 LSC allows a 6-inch projection into the corridor [see 19.2.3.4(4)], but CMS’ Final Rule published April 4, 2016 said they will enforce the more restrictive 4-inch maximum projection into the corridor, based on the Americans with Disabilities Act (ADA). For all healthcare facilities that receive Medicare & Medicaid funds, they must comply with CMS’ exception to the 2012 LSC.  

To answer your question, there are no exceptions to the 4-inch maximum projection rule. So, anything projecting more than 4 inches into the corridor, including fire extinguishers and telephones, would likely be cited by a surveyor or inspector. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 

See the latest posts on our homepage


Share

Topic Area: Regulations, Codes & Standards


Recent Posts
Recent Posts
Focus: Facility Design

Designing for introverts and extroverts


Private spaces energize introverts and social spaces energize extroverts, according to an article on the Healthcare Design website

2/15/2019

Blog

A crash course in GRC for the healthcare industry


Healthcare facilities must take the time to ensure that all employees are educated on governance, risk and compliance (GRC) when it comes to information security

2/15/2019

Focus: Facility Design

Balancing sustainable design and efficiency


Upgrades to green building standards have provided a solid framework

2/15/2019

Health system energy investments support carbon goal


Kaiser Permanente purchases wind, solar and battery energy

2/15/2019

Focus: Plumbing

Study says removing sinks from ICU cuts bacterial colonization


'Water-free' patient care can reduce the number of ICU patients colonized with gram-negative bacteria

2/15/2019





Post Comment




FREE
NEWSLETTER

News & Updates • Webcast Alerts • Building Technologies

All fields are required.