Focus: Fire-Life Safety / Column

Life Safety Q&A: Four-inch corridor projection

By Brad Keyes / Special to Healthcare Facilities Today
August 2, 2017

Q: With the adoption of the new 2012 Life Safety Code by CMS, we had a discussion about projections from the corridor wall. Since the LSC only allows projections to be 4 inches, the question that came up was in regards to fire extinguishers mounted to the wall and not recessed as they project out from the wall about 7 inches. Will we be required to recess them or will they be allowed? The same question was raised about wall mounted telephones?

A: Actually, the 2012 LSC allows a 6-inch projection into the corridor [see 19.2.3.4(4)], but CMS’ Final Rule published April 4, 2016 said they will enforce the more restrictive 4-inch maximum projection into the corridor, based on the Americans with Disabilities Act (ADA). For all healthcare facilities that receive Medicare & Medicaid funds, they must comply with CMS’ exception to the 2012 LSC.  

To answer your question, there are no exceptions to the 4-inch maximum projection rule. So, anything projecting more than 4 inches into the corridor, including fire extinguishers and telephones, would likely be cited by a surveyor or inspector. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 

See the latest posts on our homepage


Share

Topic Area: Regulations, Codes & Standards


Recent Posts
Recent Posts

Ebola epidemic spreads to larger city in Congo


Cases have been reported in a city of more than a million people

12/14/2018

Ohio healthcare facilities constantly review security procedures


Recent shootings across the country have hospital officials evaluating policies

12/14/2018

Hospital sprinkler system violations can be dangerous


Data cables contacting sprinkler lines comprise nearly 2/3 of all sprinkler line load deficiencies

12/14/2018

Privacy curtains and sheets can harbor pathogens


Soft surfaces can fly under the radar in the spread of infectious agents

12/14/2018

Calif. hospital vows to reopen after wildfire


Feather River Hospital says reopening a matter of when, not if

12/14/2018





Post Comment




FREE
NEWSLETTER

• News and Updates
• Webcast Alerts
• Building Technologies



All fields are required.