Life Safety Q&A: Un-sprinklered high-rise hospitals

By Brad Keyes / Special to Healthcare Facilities Today
August 16, 2017

Q: I am a consultant and I have a client who has a new high-rise hospital that is not fully sprinklered. The plans for this hospital were approved and stamped by the local building officials after 2003 and the building construction completed in 2010. Would the entire building have been required to be fully sprinklered when it was constructed?

A: I would say so. Depending on who they are accredited by, and what state they are in, they could be cited for not being 100% sprinklered, since the building design was approved after the 2000 Life Safety Code was adopted.  For example, if they are Joint Commission accredited, Joint Commission had been adopting the new editions of the Life Safety Code soon after NFPA published them, up to and including the 2000 edition.

So, that means since the 1991 edition of the Life Safety Code was the first edition to require all new construction healthcare occupancies to be fully protected with sprinklers, this building would have been required to be sprinklered if they were Joint Commission accredited. Also, most states adopt new versions of the LSC as they are published, so from a state viewpoint this building would likely have been required to be 100% sprinklered as well.

CMS adopted the 2000 edition of the LSC in March, 2003. Previously they were on the 1985 edition which did not require new construction to be protected with sprinklers. So, for CMS certified hospitals, the start date for new construction required to be sprinklered was March, 2003. For Joint Commission accredited hospitals, it would have been when they adopted the 1991 edition of the Life Safety Code. So, it is apparent someone did not get the word that a newly constructed high-rise hospital that had their design stamped by the local authorities after 2003, is required to be fully sprinklered.

Yep… that is a citation waiting to be written. Could even be a Condition Level Finding. Better advise them to get started in completing the sprinkler installation as soon as possible.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



See the latest posts on our homepage


Topic Area: Regulations, Codes & Standards

Recent Posts
Recent Posts
Blog: Focus: HVAC

Customers, research & development are lifeblood of evaporative cooling tower innovations

Customers actively seek energy efficiency, easy installation, low maintenance and operational reliability


Focus: Security

Alaska psychiatric hospital investigated for workplace safety issues

Workplace safety issues and fear of retaliation at Alaska's state-run Alaska Psychiatric Institute will be probed


N.Y. long-term care center has bistro with kosher foods, Ommegang

Senior care center built a bistro where residents and families can 'eat out' while staying in


Colorful medical center planned for Chicago neighborhood

The brightly-colored facility will include multi-purpose communal spaces to host wellness-related educational programs


Epson LABELWORKS PX Launches the LW-PX300 Label Printer


Post Comment


• News and Updates
• Webcast Alerts
• Building Technologies

All fields are required.