Focus: Fire-Life Safety / Column

Q&A: Oxygen cylinders in fire rated cabinets

Brad Keyes discusses storing oxygen cylinders in fire rated cabinets

By Brad Keyes / Special to Healthcare Facilities Today


Q: In regards to oxygen cylinder storage, if the quantity of gas in storage is between 300 and 3000 cubic feet in a smoke compartment and the full cylinders are being stored in a fire-rated medical gas cabinet, the hospital was told that they do not need to be stored in a specially designated room. They were told the fire-rated cabinets act as a room themselves and they could place the cabinets anywhere in the smoke compartment. I believed that the cabinets allowed the cylinders to be stored without the separation from combustibles. Question is: What is permitted?

A: I believe you are correct. Section 11.3.2 of the NFPA 99-2012 says storage of non-flammable gases greater than 300 cubic feet but less than 3,000 cubic feet shall comply with the requirements of 11.3.2.1 through 11.3.2.3.

Section 11.3.2.1 says storage locations shall be outdoors or within an enclosed interior space of noncombustible or limited combustible construction, with doors that can be secured against unauthorized entry.

Section 11.3.2.2 says oxidizing gases cannot be stored with flammable gases, liquids or vapors.

11.3.2.3 says oxidizing gases must be separated from combustibles by one of the following:

  • Minimum of 20 feet

  • Minimum of 5 feet if the entire storage location is sprinklered

  • Enclosed cabinet on noncombustible construction having a minimum fire protection rating of ½ hour.

So… there you have it. Those yellow “Fire Cabinets” are double-walled construction and really only rated for 30 minutes and they are commonly called “NFPA 30” cabinets.  But they are permitted to be used in lieu of having to meet the 5 foot or 20 foot distance requirement inside a designated room that is constructed with noncombustible or limited combustible materials, and has a door that is lockable. Limited combustible materials are traditionally gypsum wall board that has a thin layer of paper on the surface. 

But make no mistake about it… while the oxygen cylinders may be stored inside the metal cabinets, they still must be stored inside a designated room with a lockable door.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

 

 



November 16, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


Jackson Hospital Falls Victim to Third-Party Cybersecurity Incident

Jackson Hospital has no evidence that any personal information has been or will be used for identity theft as a direct result of this incident.


Making Healthcare Lighting Retrofits Work

Effective operational planning determines whether a retrofit project improves a facility or creates new problems.


Stadium Design is Reshaping Healthcare Facilities

Hospitals are turning to the sports industry for innovative ways to support healing and improve the patient experience.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.