Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: ABHR dispensers

Brad Keyes discusses regulations for ABHR dispensers

By Brad Keyes / Special to Healthcare Facilities Today


Q: In a business occupancy building, can alcohol-based hand-rub  (ABHR) dispensers be placed over carpeted area with no sprinklers?

A: Maybe yes and maybe no… It all depends on which AHJ is looking at your business occupancy.

Section 19.3.2.6 (8) of the 2012 LSC requires ABHR dispensers that are mounted over carpets, to only be in sprinklered smoke compartments. But this only applies to healthcare occupancies, and section 21.3.2.6 has similar language for ambulatory healthcare occupancies. The problem is, there is nothing written in chapters 38 or 39 regarding the installation of ABHR dispensers in business occupancies.

Since nothing is written in the business occupancy chapters, one may think there are no limitations, and the ABHR dispensers may be placed wherever you want without regard to regulations. Some AHJs may agree, and allow the ABHR dispensers be installed over carpet in an unsprinklered area. But the AHJs with healthcare experience and knowledge probably will not, based on their understanding of chapters 19 and 21. And, this is not an incorrect process, since they know these regulations regarding ABHR dispensers and can apply them to a business occupancy based on safety-related issues. Section 4.6.1.2 supports this concept.

But please understand, section 8.7.3.2 of the 2012 LSC prohibits the handling and storage of flammable liquids where it would jeopardize egress. This means ABHR dispensers are not permitted in egress corridor. Chapter 18/19 and 20/21 specifically permit ABHR dispensers in corridor so that over-rides section 8.7.3.2.  But the business occupancy chapters 38 and 39 do not have this language to over-ride 8.7.3.2, so that means ABHR dispensers are not permitted in egress corridor of business occupancies.

My advice is follow the same regulations for ABHR dispensers found in 19.3.2.6 for business occupancies, with the exception that ABHR dispensers are not permitted in egress corridors of business occupancies.  

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



August 8, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


The Children's Center of Hamden Reports Data Security Incident

The incident was detected on December 28, 2024.


Designing for Senior Care Communities Means Designing for Everyone

No spaces can be designed for just one person, designers need to think about everyone who will occupy the space.


Harlem Hospital Legionnaires' Outbreak Highlights Cooling Tower Risks

Seven deaths linked to the cooling towers underscore the need for stricter water system monitoring and preventive maintenance in healthcare settings.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.