Regulations, Codes & Standards Q&A: Aluminum astragals

Brad Keyes discusses regulations for aluminum astragals

By Brad Keyes / Special to Healthcare Facilities Today


Q: We used our recently updated Life Safety drawings to have our fire doors inspected. The inspector cited us for aluminum astragals on 13 doors. His report stated that they should be changed to steel. My boss asked me to confirm that this is fact. What are your thoughts?

A: The inspector may know something. All hardware installed on fire-rated door assemblies must be listed for use on fire-rated door assemblies, and this includes astragals. Do you have the specification sheets for the astragals that you installed? If not, can you obtain them?

Look on the specification sheets for anything that says the astragals are listed by an independent testing laboratory (UL, Intertek, ETL, etc.) for use on fire-rated door assemblies. If you find that they are listed for use on fire-rated door assemblies, then you are good to go. Photo-copy that information and send it to the inspector for his/her review.

If the specification sheets do not say the astragals are listed for use on fire-rated door assemblies, then the inspector is correct and you would have to remove them. The issue is not whether they are made with steel or aluminum, but whether they are listed for use on fire-rated door assemblies. Perhaps the inspector believes that aluminum astragals are not listed?   

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



March 14, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Why Healthcare Facilities Management Is Critical to Patient Safety 

Hospitals and other healthcare facilities rely on much more than doctors and nurses to keep patients safe.


Brookdale Senior Living Announces Acquisition of the Brookdale Galleria Community

The 244-unit independent living and assisted living community is located directly adjacent to The Galleria shopping and entertainment complex.


Erlanger Health System Falls Victim to Data Breach

Erlanger has no evidence of any improper use of the information because of this incident.


Technological Readiness: The Missing Construction Milestone

A new building can be complete by most measures but still not be technologically or operationally ready.


From Cooling Towers to Cost Savings: Hospital Seizes Power-Saving Opportunity

Case study: Arkansas hospital increases energy efficiency by diagnosing cooling tower issues and treating its entire mechanical system.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.