Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Battery-charging room

Brad Keyes discusses regulations for battery-charging rooms

By Brad Keyes / Special to Healthcare Facilities Today


Q: Are there any Life Safety Code requirements for a battery-charging room, such as HVAC pressurization and air changes per hour (ACH) rates? These rooms are where I charge my EVS floor machines.

A: I guess it would depend on how the room is interpreted in regards to its function. According to the 2014 FGI Guidelines, which references the ASHRAE 170 table, a janitor’s closet must be negative, have 10 ACH, the air in the room must be exhausted to the outdoors, you cannot have a room HVAC that recirculates air, and there is no design requirements for humidity and temperature.

If the room is a hazardous material storage (which sounds more like it), the room would have to meet the same requirements as listed above, with the added requirement that there is 2 ACH of outdoor air.

But those are for new construction. For existing conditions, you would have to comply with the FGI or AIA requirements in effect at the time of the design of the room.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



September 11, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

Cleanliness in Hospitals: Clinical Priority and Community Perception

EVS managers and communities value cleanliness for complementary reasons: managers for safety and compliance, communities for trust and comfort.


Dana-Farber Receives $50M Gift for Planned Cancer Hospital

A $50 million grant from the Yawkey Foundation will support construction of Dana-Farber Cancer Institute’s planned 450,000-square-foot cancer hospital.


Clarinda Regional Health Center Reports Data Security Incident

On or around December 15, 2025, Clarinda learned that certain data within its network may have been accessed without authorization.


Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.