Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Door frames

Brad Keyes discusses regulations for door frames

By Brad Keyes / Special to Healthcare Facilities Today


Q: I had an independent Life Safety inspection and during the inspection the inspector cited me for my 2-hour fire door frames not having a fire rating visible. I explained that we went to a fire rated continuous hinge on these doors that covered the labels. He said that that was not enough, he needed to see a label. Should I remove each hinge and take a picture of the fire rating labels?

(The reply for this question comes from Lori Greene, Manager of Codes & Resources at Allegion. Visit Lori’s website on doors and hardware at www.idighardware.com)

A: This topic has come up before, and I asked some AHJs about it since the answer is not found in the codes and standards.  The consensus was that the label should be documented with photos before the hinges are installed – close-up photos to show what is written on the label, and wider photos to show the location of the door.

I’m sure it’s a pain to get this documentation now, but I think that’s the only way to do it for a retrofit situation unless you want to have the doors relabeled.  For new doors and frames, the labels can be applied in another location – on the frame head, and for the doors – either on top or on the lock edge.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



March 28, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Wesley Rehabilitation Center Specializes in Patients from Design to Care

Barge knew that patients were at the core of the design process.


Casa Colina Center for Disorders of Consciousness Officially Opens

New program addresses critical need for patients with severe brain injuries.


Legionella Detected at Michigan Health Facility

Case follows a similar finding of Legionnaires’ disease in a former patient.


Crystal Spring Tower Opens at Carilion Roanoke Memorial Hospital

The new cardiovascular institute improves access and care across the region.


Hospital Evacuation Highlights Importance of Emergency Preparedness

Berger Hospital was evacuated after smoke was discovered in the basement.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.