Q: How long is a grace period for the annual fire pump test to be past due?

A: Well, technically, there is no grace period. Either you are compliant or you are not. But most AHJs usually have their way of determining time when it involves frequencies for testing and inspection.

One AHJ may be “by the NFPA book” and when the NFPA code or standard says annually, that means it needs to be done during the calendar year. So, an annual flow test could be done in May one year and it could be done in September of the next year.

But accreditation organizations (AO) seem to have a stricter interpretation of time. Where NFPA says annually, one AO could mean 12 months from the previous test, plus or minus 30 days. But CMS does not like the “plus” side of the equation, meaning they don’t mind if you do your flow-test before 12 months has pass from the last test, but they don’t care for one day beyond 12 months. So, state agencies surveying on behalf of CMS would likely cite an organization if the test is one or more days beyond 12 months from the last test.

This is one area where NFPA has not clearly defined how they interpret the different time periods for testing or inspection. They purposefully leave this open for the AHJ to decide, but the problem is, hospitals typically have 5 or 6 different AHJs who inspect them for compliance with the Life Safety Code. Chances are, you will never get all 5 or 6 AHJs to agree on what it means. It’s a crap-shoot sometimes. You don’t know how one particular AHJ will respond until they are onsite and write a citation. So, the hospital has to follow the most restrictive interpretation.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



June 20, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

The Future of the Global Hospital Hygiene Market

A market study details the current state of the global hygiene market and the factors that are expected to make a big difference in the next decade.


Rethinking Fire Safety Inspections

Digital tools bridge the gap between growing facility complexity and workforce limitations, allowing teams to maintain the highest safety standards.


The Ohio State University Wexner Medical Center Officially Opens

With the new hospital comes other changes, including new street and building names on the medical campus.


Healthcare and Resilience: A Pledge for Change

Climate resilience and reducing environmental impact drive voluntary program targeting hospitals.


Texas Health Resources Announces New Hospital for North McKinney

Expected to open in 2028, the hospital will feature 60 beds initially with plans to double in capacity to accommodate for future community growth.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.