Regulations, Codes & Standards Q&A: Signage inside a stairwell

Brad Keyes discusses regulations for signage inside a stairwell

By Brad Keyes / Special to Healthcare Facilities Today


Q: Can signage, other than that specifically required for inside a fire exit stairwell according to the LSC, be placed inside a fire exit stairwell?

A: Technically… no. According to section 7.1.3.2.3 of the 2012 LSC, it says the exit enclosure shall not be used for any purpose that has the potential to interfere with its use as an exit, and if so designated, as an area of refuge. The Annex section of A.7.1.3.2.3 says the intent is the exit enclosure essentially be ‘sterile’ with respect to safety hazards.

But, it probably depends on the signage that you want to install in the exit enclosure. If the signage is truly tight to the wall surface and cannot interfere with exiting, then most surveyors would not say anything. But if the signage was in the same style as a hanging framed picture, then that would likely be cited, since it could interfere with exiting when someone brushed their shoulder against the framed picture and it falls off the wall and becomes a trip hazard, or if it was tight to the wall, the projection of the frame could be an interference as well.  

But, the Annex section says the stairwell should be sterile… so a technical interpretation could say nothing can be in the stairwell.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



August 22, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Reframing the Construction Manager as a Community Manager

Managers must work with patients, community residents and other interested parties to ensure a smooth, successful construction projects


Health First Celebrates 'Topping Off' Ceremony for New Cape Canaveral Hospital Campus

Construction is slated to finish by the end of 2026 or early 2027.


The University of Hawai'i Cancer Center Caught Up in Cyberattack

Investigations are still ongoing to assess other sensitive information that may have been impacted.


Mature Dry Surface Biofilm Presents a Problem for Candida Auris

Multiple methods are described in the literature, but no consensus has been reached for disinfection efficacy tests against biofilms.


Sutter Health's Arden Care Center Officially Opens

With an adaptive reuse of an underutilized office building, the 70,000 square-foot facility was renovated to meet current healthcare standards.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.