Q: I have two questions regarding spark-ignited emergency power generators:

1. What maintenance tests are required for natural or propane generators?

2. Are load bank test required for natural gas or propane gas powered generators?

A: Monthly tests, but since they are spark-ignited generators they do not have to meet a particular load. They just have to operate with the available EPSS load for a minimum of 30 minutes or until the water temperature and oil pressure have stabilized. (See section 8.4.2.4 of NFPA 110-2010).

No, spark-ignited generators are not required to have an annual load bank tests. An annual load bank test is required when diesel powered generators cannot meet the minimum load of 30% of the nameplate rating (in kW) during each monthly load test. Spark-ignited generators are exempt from having to meet this requirement. 

A 3-year 4-hour load test is required for all generators, including spark-ignited generators. But you are not permitted to use a load bank on spark-ignited generators. The 3-year 4-hour load test must operate using the load from the ATS. For spark-ignited generators, the load is permitted to be the available load. (See section 8.4.9.5.3 of the NFPA 110-2010.) Load banks are not permitted for the 3-year 4-hour load test for spark-ignited generator.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



April 18, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


The Children's Center of Hamden Reports Data Security Incident

The incident was detected on December 28, 2024.


Designing for Senior Care Communities Means Designing for Everyone

No spaces can be designed for just one person, designers need to think about everyone who will occupy the space.


Harlem Hospital Legionnaires' Outbreak Highlights Cooling Tower Risks

Seven deaths linked to the cooling towers underscore the need for stricter water system monitoring and preventive maintenance in healthcare settings.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.