Regulations, Codes & Standards Q&A: Two-hour separations between hospitals

Brad Keyes discusses regulations for two-hour separations between hospitals

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have a client that is building a new Women’s and Children’s Hospital. The women's component will be licensed to one organization, and the children's component will be licensed to another. Both organizations intend to operate separately and self-sufficient but would like the new building to look like one comprehensive hospital building. Is a two-hour occupancy separation required between the two, separately licensed hospitals in the same building?

 

 

A: As long as the occupancy designation is the same for both unit, then no… a two-hour fire rated separation is not required according to the Life Safety Code but check with your state and local authorities to see if they have more restrictive requirements.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



January 16, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

Creating Healthcare Campus Master Plans That Allow Movement and Respite

A thoughtful campus master plan looks beyond buildings to the corridors and transitional spaces that shape how people experience healthcare environments.


Aspirus Health Celebrates Opening of Chippewa Falls Hospital and Clinic

The new facility combines hospital and clinic services in one location and is designed to support patients with coordinated, patient-centered care.


AdventHealth to Open Aurora Highlands Medical Campus

AdventHealth Aurora Highlands includes a 24-hour freestanding emergency room, outpatient imaging and clinic services.


The Future of Healthcare Facility Construction Projects

Brian Cowperthwaite highlights the invisible work that impacts everyone who walks through a healthcare facility.


Arnprior Regional Health Upgrades Building Controls to Improve IEQ

Case study: They wanted to improve the hospital facility’s IEQ to support patient care and reduce long-term operating costs.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.