Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Ceiling tile replacement

Brad Keyes discusses regulations for ceiling tile replacement

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have several ceiling tiles (approximately 52) that are scratched or damaged that has sprinkler heads in them. Is there a code that references or mandates the replacement of the ceiling tiles? Also, I was told once the old/current sprinkler heads are removed to replace the ceiling tiles, new sprinkler heads have to be replaced. Is that true?

A: If the ceiling tiles are stained, most surveyors will have a problem with that as that implies water which can lead to mold or mildew. If they cite the stained ceiling tiles, it would be likely be cited under an Infection Control standard.  

If the ceiling tiles have gaps or cracks wider than 1/8-inch then that will likely be cited under a sprinkler installation standard or a smoke detector installation standard, as the ceiling needs to resist the passage of smoke in order for the smoke detectors and/or sprinkler to function properly. 

But a ceiling tile that is scratched is not a Life Safety Code deficiency and likely would not be cited. 

Yes… you cannot re-install used sprinklers (see section 6.2.1 of NFPA 13-2010), so if you need to remove the sprinkler head to change the ceiling tiles, then that is a great time to update to a newer style that uses escutcheons that are removable to allow easy replacement of ceiling tiles.   

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



March 18, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

Every Detail Matters: A Patient's Story of Healing, Hope and Healthcare Facilities

In the Facilities in Focus season finale, 11-year-old Kendalynn and her mother share how Intermountain Primary Children’s Hospital became more than a place for care.


Enhancing Safety at Hennepin Healthcare with a Screening System

Case study: The system was able to detect 2,500 risk items in less than five months.


The Landes Group Completes Acquisition of Encore Medical Center

Encore Medical Center is a 108,055-square-foot hospital in Bryant, Arkansas.


What Managers Miss in Small and Mid-Sized Cooling Units

The assumption is that small cooling units are fine. That assumption is costing facilities more than most owners and managers realize.


Preparing Healthcare Facilities for Cockroach Risks

Here’s what healthcare facilities managers should inspect and address after severe weather to prevent pest problems.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.