Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: EM lights in MRI

Brad Keyes discusses regulations for EM lights in MRI

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have a question on the requirement for the battery backup lighting inside the MRI suites. We are in the process of building two new MRI centers and I am receiving a lot of push back from the Project Engineer.

This engineering group specializes in MRI projects and they tell me they never install battery backup lighting and that NFPA 99 does not require battery backup lighting anywhere outside of an operating room. I was told to reference 6.3.2.2.11.2 of NFPA 99-2012 which specifically mentions operating rooms. My reply was that 6.3.2.2.11.1 does not specify only operating rooms so it is much broader in scope and since we use anesthesia in the MRI it would be required.

Before I stir up the pot anymore with the engineering firm I wanted to make sure that if Anesthesia is being used in the MRI room that emergency battery backup lighting should be in place.

A: Yes… you are correct. NFPA 99-2012, section 6.3.2.2.11.1 requires one or more battery-powered lighting units within locations where deep sedation and general anesthesia is administered. That includes MRI areas, Cath Lab areas, and of course, Operating Rooms and Procedure rooms. ICUs and NICUs would typically not be included.

Just because the project engineer from the contractor has never been told to install battery powered lighting units before does not preclude the fact that it is a requirement and it is enforced by CMS and the Accreditation Organizations. The engineer is mistaken. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



July 24, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

Seeking Standards for Microbial Loads in Healthcare Facilities

Why is there no binding standard for the acceptable microbial load on surfaces or in the air in hospitals?


UCR Health Unveils Plans for Major Expansion

The vision for the site will include an outpatient diagnostic center and possible future expansion.


High-Performance Windows Support Safety at UW Medicine's New Behavioral Health Center

Case study: Engineered for strength, quiet and daylight, the chosen windows help create a safe, calming and energy-efficient environment for patients and providers.


Central Maine Healthcare Dealing with IT System Outage

The organization identified unusual activity within their computer software, prompting them to secure and shut off all IT systems.


Kaiser Permanente Opens Newly Expanded Everett Medical Center

The facility offers primary care and pediatric care and has specialty care departments.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.