Regulations, Codes & Standards Q&A: Fire damper testing in surgery centers

By Brad Keyes / Special to Healthcare Facilities Today
February 5, 2020

Q: We are looking for some clarification on fire damper testing requirements as we recently had inspections done at our surgery center. One contractor says dampers with fusible links require the links be replaced once they are tested, so does that mean that we have to test and then replace them each time or is there a different requirement for that type specifically? 

A: Fire dampers must be tested in accordance with NFPA 80-2010, chapter 19. Section 19.4.4 says If the damper is equipped with a fusible link, the link shall be removed for testing to ensure full closure and lock-in place if so equipped. Section 19.4.8 says the fusible link shall be reinstalled after testing is complete. Section 19.4.8.1 says if the link is damaged or painted, it shall be replaced with a link of the same size, temperature, and load rating.

There is no requirement in NFPA 80-2010 to automatically replace the link every time the damper is tested. Perhaps there may be some confusion with the annual testing of fire dampers in the kitchen hood exhaust system which does require automatically replacing the fusible links every time those dampers are tested, but that’s not part of NFPA 80.  

Section 19.4.11 says periodic inspections and testing of a combination fire/smoke damper shall also meet the inspection and testing requirements contained in Chapter 6 of NFPA 105, Standard for Smoke Door Assemblies and Other Opening Protectives. So, a combination fire/smoke damper would have to comply with both NFPA 80 and NFPA 105. 

Section 6.5.5 of NFPA 105-2010 says where a fusible link is installed on a combination fire/smoke damper, the fusible link shall be removed for testing the damper for full closure simulating a fire condition per the requirements and frequencies of 19.5.4 of NFPA 80, Standard for Fire Doors and Other Opening Protectives. So, if a fusible link exists in a combination damper then you comply with the requirements of NFPA 80 in removing the link for the test. There are no requirements to automatically replace the link.

 

 

NFPA 105 continues to explain that smoke dampers are tested once every 4-years for non-hospitals and must be tested with normal HVAC airflow. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

See the latest posts on our homepage


Share

Topic Area: Regulations, Codes & Standards


Recent Posts
Recent Posts

Fire Safety and Cybersecurity: What’s the Connection?


Attacks can create false alarms, loss of communication or denial of service, and a malfunctioning system could compromise patient safety

6/24/2021

Texas Cancer Center Breaks Ground


Facility will include 30,000 square feet of clinic space for medical oncology, radiation oncology, and gynecologic oncology services

6/24/2021

Data Breach Affects 21 Hospitals. 1.6 Million People


Compromised files contained patient records with protected health information

6/24/2021

Rise of Delta Variant Puts Facilities on Notice


More-harmful coronavirus variant probably will become dominant U.S. strain in the coming months, Walensky says

6/23/2021

Wanted: A 21st Century IAQ Strategy


Managers need to consider holistic integrated IAQ solution that uses complementary technologies

6/23/2021





Post Comment




FREE
NEWSLETTER

News & Updates • Webcast Alerts • Building Technologies

All fields are required.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.