NFPA sprinkler system maintenance standard gets a revamp for 2014 edition

Significant revisions to standard NFPA 25, Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, have been put into place for the 2014 edition.

By Healthcare Facilities Today


Significant revisions to NFPA 25, Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, have been put into place for the 2014 edition of the standard. An article in NFPA Journal walks through the major changes. Here are six changes facility managers should be aware of.

1. Fire pump operating test frequency. Chapter 8 now requires electric-driven pumps to be tested weekly if they are located in high-rises, are electric-driven vertical turbine pumps or use limited service controllers. Otherwise, the current monthly testing interval generally still applies.

2. Diesel fuel quality check. An annual test of diesel-driven fire pump's fuel supply for fuel quality is now required.

3. Definition of ‘sprinkler system.’ Adopting the NFPA 13 2013 edition definition, in a high-rise facility NFPA 25 now defines a sprinkler system as the piping that is downstream of a floor control valve assembly. This means that each floor could conceivably have an individual sprinkler system each subject to inspection, testing and maintenance requirements. Previously, spot testing only a few floors in a high rise would suffice.

4. Internal assessments. Formerly referred to as "internal inspection," this change requires inspecting the inside of the pipe on a five-year interval for degradation, obstruction or organic growth, such as zebra mussels. This applies to each sprinkler system in the facility (See #3.)

5. Water mist systems. Inspection, testing and maintenance requirements for water mist systems are now governed by NFPA 25 and no longer will be found in NFPA 750.

6. Valve status test. A valve status test is now required when a valve is returned to service. This quick test is current common practice among inspection companies to confirm that water is flowing through the control valve and helps to guard against the most common cause of sprinkler system failure.

Read the article.



May 31, 2013


Topic Area: Safety


Recent Posts

Case Study: How NYU Langone Rebuilt for Resilience After Superstorm Sandy

Although the damage was severe, it provided a valuable opportunity for NYU Langone to assess structural vulnerabilities and increase facility resilience.


Frederick Health Hospital Faces 5 Lawsuits Following Ransomware Attack

The lawsuits accuse FHH of inadequate cybersecurity, poor breach notification and failing to protect patients from identity theft risks.


Arkansas Methodist Medical Center and Baptist Memorial Health Care to Merge

They have signed a non-binding letter of intent to complete a shared mission agreement to merge the two organizations.


Ground Broken on Intermountain Saratoga Springs Multi-Specialty Clinic

The clinic is scheduled to open and start seeing patients in the fall of 2026.


Electrical Fire Tests Resilience of Massachusetts Hospital

Signature Healthcare Brockton Hospital used opportunity to renovate key systems and components and expand facility operations.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.