Q&A: Fire door annual test and inspection

Brad Keyes discusses fire door annual test and inspection

By Brad Keyes / Special to Healthcare Facilities Today


Q: I'd like some clarification concerning the new requirement for annual fire door inspections: NFPA 101 2012, Chapter 7.2.1.15 States "Where required by Chapters 11 through 43, the following door assemblies shall be inspected ....". I haven't found anything in Chapters 18 or 19 that specifically require the annual inspection. Additionally, the NFPA 101 Handbook specifically states that only occupancies requiring inspections are Assembly, Educational, Day-Care and Residential board and care. My question is where is the specific reference that is requiring hospitals to conduct annual fire door testing?

A: You almost had it correct…Section 7.2.1.15 of the 2012 LSC is a sub-heading titled “Inspection of Door Openings”. What you stated was actually section 7.2.1.15.1 which does not refer to fire-rated doors, but to certain doors in high-traffic areas, or doors of high importance, such as doors equipped with panic hardware, doors in exit enclosures, electrically controlled doors, or doors with special locking arrangements. Now some of these doors may be fire-rated, but section 7.2.1.15.1 does not specifically refer to fire-rated doors. Therefore, that is why this section is only required if the occupancy chapter requires it and you’re correct in saying the healthcare occupancies do not require it.

But look at section 7.2.1.15.2 which says “Fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80…” This is the section that applies to all occupancies because it does not say “Where required by Chapters 11 through 43…” Section 19.2.2.2.1 in the existing healthcare occupancy chapter says doors must comply with section 7.2.1. So… you still have to test and inspect your fire rated door assemblies on an annual basis, because section 7.2.1.15.2 says you have to.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



April 19, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Upward Mobility: Market Forces Drive Hospitals Higher

Healthcare facilities nationwide are navigating challenges and opportunities presented by expanding their reach into the sky.


Georgia Hospital Bomb Hoaxes Highlight Need for Healthcare–Police Partnerships

Proactive planning and close collaboration with law enforcement help healthcare facilities maintain safety and continuity during false threats.


MUSC Health Celebrates Groundbreaking for Nexton Hospital and Ambulatory Cancer Facility

The Nexton cancer facility is expected to open in summer 2027, and the Nexton hospital in summer 2028.


Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.