Q&A: Fire door annual test and inspection

Brad Keyes discusses fire door annual test and inspection

By Brad Keyes / Special to Healthcare Facilities Today


Q: I'd like some clarification concerning the new requirement for annual fire door inspections: NFPA 101 2012, Chapter 7.2.1.15 States "Where required by Chapters 11 through 43, the following door assemblies shall be inspected ....". I haven't found anything in Chapters 18 or 19 that specifically require the annual inspection. Additionally, the NFPA 101 Handbook specifically states that only occupancies requiring inspections are Assembly, Educational, Day-Care and Residential board and care. My question is where is the specific reference that is requiring hospitals to conduct annual fire door testing?

A: You almost had it correct…Section 7.2.1.15 of the 2012 LSC is a sub-heading titled “Inspection of Door Openings”. What you stated was actually section 7.2.1.15.1 which does not refer to fire-rated doors, but to certain doors in high-traffic areas, or doors of high importance, such as doors equipped with panic hardware, doors in exit enclosures, electrically controlled doors, or doors with special locking arrangements. Now some of these doors may be fire-rated, but section 7.2.1.15.1 does not specifically refer to fire-rated doors. Therefore, that is why this section is only required if the occupancy chapter requires it and you’re correct in saying the healthcare occupancies do not require it.

But look at section 7.2.1.15.2 which says “Fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80…” This is the section that applies to all occupancies because it does not say “Where required by Chapters 11 through 43…” Section 19.2.2.2.1 in the existing healthcare occupancy chapter says doors must comply with section 7.2.1. So… you still have to test and inspect your fire rated door assemblies on an annual basis, because section 7.2.1.15.2 says you have to.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



April 19, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

5 Reasons Engineering is the Edge in Healthcare Master Planning

The most successful plans go further to unlock smarter investments, improve resilience and enable better patient outcomes.


Building an AI-Ready Healthcare Facility 

Creating a secure, standardized data foundation can help facilities teams put AI to work more effectively.


Family Medical Associates of Raleigh Reports April 2026 Data Breach

The investigation has found evidence that between April 18, 2026, and April 20, 2026, an unauthorized actor intermittently accessed some FMAR systems.


Every Detail Matters: A Patient's Story of Healing, Hope and Healthcare Facilities

In the Facilities in Focus season finale, 11-year-old Kendalynn and her mother share how Intermountain Primary Children’s Hospital became more than a place for care.


Geisinger Wyoming Valley Medical Center Tops Off New 11-Story Tower

The expansion will improve the patient experience by transitioning the hospital to all private patient rooms while significantly increasing clinical capacity.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.