Column

Q&A: New testing and inspection requirements

Brad Keyes discusses new testing and inspection requirements

By Brad Keyes / Special to Healthcare Facilities Today


Q: I met with our facility engineer and CEO on the required inspections to be compliant with the new 2012 Life Safety Code prior to November of this year. I stated that all testing would need to be completed prior to November, which included the smoke and fire damper tests which are due every 6 years, along with the standpipe flow tests which are due every 5 years.  Ours are not due until 2019. The CEO is wanting to see the requirement that these must be performed “early” by November of 2016 in writing. I may have stated this requirement to them incorrectly.  If so, please let me know.  Could you please direct me to where I can find documentation to back up the requirements?

A: The new requirements called for in the 2012 Life Safety Code need to be completed by November 1, 2016… not the existing requirements. If you last performed fire damper tests in 2013, then you do not have to do them again until 2019. There is no requirement to perform existing tests by November 1, 2016.

New requirements (testing and inspection) that are called for in the 2012 LSC that were never required before, and which you need to have completed by November 1, 2016 are:

Fire door testing (all side-hinged fire door assemblies need to be tested annually)

• Fire hose valve inspections (quarterly)

• Fire hose valve tests (2.5 inch annually; 1.5 inch every 3 years)

• Sprinkler pipe inspections (every 5 years)

• One main drain test if sprinkler water is through a backflow preventer (quarterly)

• Fire drills in OR (annually)

The point is… these items above are new requirements, something that was never required before. Some are quarterly… some are annually… and some are required less frequent than annually. But the first test/inspection must be completed by November 1, 2016. CMS says in their S&C memo 16-29 that hospitals have to be fully compliant with the 2012 LSC by then.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



September 14, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


The Children's Center of Hamden Reports Data Security Incident

The incident was detected on December 28, 2024.


Designing for Senior Care Communities Means Designing for Everyone

No spaces can be designed for just one person, designers need to think about everyone who will occupy the space.


Harlem Hospital Legionnaires' Outbreak Highlights Cooling Tower Risks

Seven deaths linked to the cooling towers underscore the need for stricter water system monitoring and preventive maintenance in healthcare settings.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.