Column

Q&A: New testing and inspection requirements

Brad Keyes discusses new testing and inspection requirements

By Brad Keyes / Special to Healthcare Facilities Today


Q: I met with our facility engineer and CEO on the required inspections to be compliant with the new 2012 Life Safety Code prior to November of this year. I stated that all testing would need to be completed prior to November, which included the smoke and fire damper tests which are due every 6 years, along with the standpipe flow tests which are due every 5 years.  Ours are not due until 2019. The CEO is wanting to see the requirement that these must be performed “early” by November of 2016 in writing. I may have stated this requirement to them incorrectly.  If so, please let me know.  Could you please direct me to where I can find documentation to back up the requirements?

A: The new requirements called for in the 2012 Life Safety Code need to be completed by November 1, 2016… not the existing requirements. If you last performed fire damper tests in 2013, then you do not have to do them again until 2019. There is no requirement to perform existing tests by November 1, 2016.

New requirements (testing and inspection) that are called for in the 2012 LSC that were never required before, and which you need to have completed by November 1, 2016 are:

Fire door testing (all side-hinged fire door assemblies need to be tested annually)

• Fire hose valve inspections (quarterly)

• Fire hose valve tests (2.5 inch annually; 1.5 inch every 3 years)

• Sprinkler pipe inspections (every 5 years)

• One main drain test if sprinkler water is through a backflow preventer (quarterly)

• Fire drills in OR (annually)

The point is… these items above are new requirements, something that was never required before. Some are quarterly… some are annually… and some are required less frequent than annually. But the first test/inspection must be completed by November 1, 2016. CMS says in their S&C memo 16-29 that hospitals have to be fully compliant with the 2012 LSC by then.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



September 14, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

The High Cost of Healthcare Violence

As workplace violence increases, healthcare facilities face mounting financial and operational disruptions- prompting legislative action.


EVS Teams Can Improve Patient Experience in Emergency Departments

A report confirmed that cleanliness of the ED was the third most impactful element on patient experience surveys.


East Tennessee Children's Hospital to Become Dolly Parton Children's Hospital

It marks a collaboration designed to elevate children's healthcare across East Tennessee.


The Future of the Global Hospital Hygiene Market

A market study details the current state of the global hygiene market and the factors that are expected to make a big difference in the next decade.


Rethinking Fire Safety Inspections

Digital tools bridge the gap between growing facility complexity and workforce limitations, allowing teams to maintain the highest safety standards.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.