Q: Does a corridor door that serves an office have to swing into the office? The office is on a patient floor and the door does not serve as any other type of door.
A: No. The door is permitted to swing into the corridor, but during its swing, it cannot obstruct more than ½ the width of the corridor. And when the door is fully open (up against the wall), it cannot extend more than 7 inches into the corridor.
If the door swings into more than ½ the width of the corridor, then that is a problem. Likewise, if the door extends out into the corridor more than 7 inches when it is fully opened, then that also is a problem.
Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs