Focus: Fire-Life Safety / Column

Q&A: Office door swing

Brad Keyes discusses office door swing requirements

By Brad Keyes / Special to Healthcare Facilities Today


Q: Does a corridor door that serves an office have to swing into the office? The office is on a patient floor and the door does not serve as any other type of door.

A: No. The door is permitted to swing into the corridor, but during its swing, it cannot obstruct more than ½ the width of the corridor. And when the door is fully open (up against the wall), it cannot extend more than 7 inches into the corridor.

If the door swings into more than ½ the width of the corridor, then that is a problem. Likewise, if the door extends out into the corridor more than 7 inches when it is fully opened, then that also is a problem.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

 

 



October 26, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Healthcare Is the New Retail

How site selection strategies are shaping the future of medical real estate.


Bridgeway Behavioral Health Services Launches Campaign to Renovate Health Center

The $2 million capital campaign aims to renovate and expand the outpatient behavioral health center in Elizabeth, New Jersey.


Ground Broken for New North Dakota State Hospital

The 300,000-square-foot facility in Jamestown will provide 140 beds in a modern, trauma-informed care environment.


AI Usage for Healthcare Facilities

People in all industries are finding more use cases for artificial intelligence.


Ground Broken on Pelican Valley Senior Living Modernization Project

It is expected to reach completion in early-mid 2027.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.