Q&A: Overhead rolling fire door

Brad Keyes discusses whether overhead rolling fire door is needed

By Brad Keyes / Special to Healthcare Facilities Today


Q: We have an existing overhead rolling fie door acting as a curtain-window between a phlebotomy area and the egress corridor that is no longer needed (like to those found in pharmacy areas to the corridor). It is currently connected to the fire system for release and also has a fusible link. We want to disconnect it from the fire system, keep it closed, and drywall the window area so that it does not appear it was ever there. The question arose, can this be done, or do we need to go through the cost to physically remove it. It is viewed by some that once it was in place it must always be tested and inspected unless completely removed. However, I see this as being similar to walling off a dumbwaiter with "2 hr. shaft-wall" when it is no longer needed. We have been allowed to do this by our state agency. What do you think?

A: I think your analogy is apt for this situation. According to sections 4.5.8 and 4.6.12.1 of the 2012 LSC, whenever a device is required for code compliance, it must be continuously maintained. But, if you close-up the opening in such a way that complies with new construction requirements, then the over-head rolling fire door is no longer needed. So, boxing in the device and abandoning in place would be acceptable.

And, according to section 4.6.12.3 of the 2012 LSC, existing life safety features obvious to the public, if not required by the code, must be either maintained or removed. Well, if you box-up and cover the overhead rolling fire door (and it is no longer required), then it is no longer obvious to the public and can be removed.

While my personal choice would be to remove the overhead rolling fire door if it is no longer needed and used, your plan to cover it up would be acceptable as long as it is no longer needed.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

Brad's webcast is scheduled for today. He'll be discussing  "New Requirements, New Challenges: The 2012 Life Safety Code."

 



December 14, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Seeking Standards for Microbial Loads in Healthcare Facilities

Why is there no binding standard for the acceptable microbial load on surfaces or in the air in hospitals?


UCR Health Unveils Plans for Major Expansion

The vision for the site will include an outpatient diagnostic center and possible future expansion.


High-Performance Windows Support Safety at UW Medicine's New Behavioral Health Center

Case study: Engineered for strength, quiet and daylight, the chosen windows help create a safe, calming and energy-efficient environment for patients and providers.


Central Maine Healthcare Dealing with IT System Outage

The organization identified unusual activity within their computer software, prompting them to secure and shut off all IT systems.


Kaiser Permanente Opens Newly Expanded Everett Medical Center

The facility offers primary care and pediatric care and has specialty care departments.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.