Q: There is a matrix floating around on the web that describes Joint Commission’s compliance for fire drills. It breaks the quarters down as Q1=January, February, March, and Q2=April, May, June, etc. Does this mean that for a first shift drill last run in April, we can have the next drill run in September and still be compliant, + or - 10 days?

A: No, not for Joint Commission. In their Overview to the Environment of Care chapter in the Hospital Accreditation Standards manual, Joint Commission says quarterly or once per quarter means “every three months, plus or minus 10 days”. Now, I’ve heard Joint Commission engineers say they will allow this to be interpreted as follows: If the drill was conducted on April 15, that means three months from April is July. July plus 10 days means August 10 and July minus 10 days means June 20. So, according to the engineers from The Joint Commission, the window of opportunity is 51 days: from June 20 to August 10. That scenario would apply to any date the drill was conducted in April.

But to be honest, the Overview of the Joint Commission manual doesn’t say that. Other people are interpreting the Overview to mean if the drill was conducted on April 15, then 3 months after that is July 15. July 15 plus 10 days is July 25, and July 15 minus 10 days is July 5. That leaves you with a 20-day window of opportunity. 20 days is significantly less than 51 days, so you will be at the mercy of the surveyor to determine which one they enforce.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

 

 



October 19, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Healthcare Security: To Arm Or Not To Arm?

Deciding whether or not to hire armed security personnel requires that managers understand a range of critical considerations.


False Alarm at Kansas Hospital Highlights Importance of Alarm System Reliability

After a two-hour search of the hospital and nearby medical facilities, no threat was found.


Integrated Oncology Network Caught Up in Data Breach

The network first learned of the incident on April 11, 2025.


ISSA Introduces Healthcare Platform to Advance Safer, Cleaner Patient Environments

This new resource integrates training, research and cross-sector collaboration to raise care standards and improve patient outcomes.


Third-Party Tracking Settlement is a Compliance Wake-Up Call for Healthcare Facilities Managers

Mount Sinai Health System agrees to a $5.3 million settlement to resolve claims it improperly shared patient data with Facebook through tracking tools.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.