Q&A: Stairwell chair lifts

Brad Keyes discusses stairwell chair lifts

By Brad Keyes / Special to Healthcare Facilities Today


Q: Can a chair lift device be installed in an exit stairwell? What are the regulations?

A: The Life Safety Code and the local building codes set minimum widths of the required exit stairwells, pertaining to the required doors to the exit stairwells, and they set a minimum number of exit stairwells the hospital must have. These are all calculated by the architect who designed the facility to accommodate people exiting the building during an emergency. To install a chair-lift device in a stairwell would violate these conditions and would cause the building to be non-compliant with the Life Safety Code.

The following sections of the 2012 Life Safety Code set the requirements for minimum widths of required egress components:

•  7.2.2.2.1.1(b) 36 inches clear width for existing stairs

•  7.2.2.2.1.2(A) 36 inches clear width for new stairs serving less than 50 occupants

•  7.2.2.2.1.2(B) 44 inches clear width for new stairs serving 50 to less than 2000 occupants

•  7.2.2.2.1.2(B) 56 inches clear width for new stairs serving 2000 or more occupants

• 19.2.3.6 The minimum clear width of doors in existing healthcare occupancies is 32 inches

• 19.2.3.7 The minimum clear width of doors in existing healthcare occupancies is 28 inches where evacuation by bed, gurney or wheelchair is required

These are minimum width requirements, and actual widths would have to increase based on the number of occupants calculated to use these components.

Section 7.2.2.5.3.1 of the 2012 LSC says nothing may be installed in exit enclosures that could interfere with egress. I suspect a chair-lift would interfere with egress.

If you have a stairwell that is not an exit stairwell, then the possibility may be that a chair-lift could be installed as long as minimum aisle widths (36 inches) are met. Check with your design professional and your state and local AHJs to determine if that is possible.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



August 17, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Mature Dry Surface Biofilm Presents a Problem for Candida Auris

Multiple methods are described in the literature, but no consensus has been reached for disinfection efficacy tests against biofilms.


Sutter Health's Arden Care Center Officially Opens

With an adaptive reuse of an underutilized office building, the 70,000 square-foot facility was renovated to meet current healthcare standards.


Insight Hospital and Medical Center Falls to Data Breach

The investigation determined that an unauthorized individual accessed the network between August 22, 2025, and September 11, 2025.


The High Cost of Healthcare Violence

As workplace violence increases, healthcare facilities face mounting financial and operational disruptions- prompting legislative action.


EVS Teams Can Improve Patient Experience in Emergency Departments

A report confirmed that cleanliness of the ED was the third most impactful element on patient experience surveys.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.