Q&A on interior finish

In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about interior finish


In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about interior finish.

Q: I would like to know the 2012 Life Safety Code (LSC) requirements for an audio testing room in a high-rise hospital. The floor, wall and ceilings are covered with cloth materials similar to carpet. The room has been protected by a smoke detector and sprinkler.

A: The wall coverings would not be considered decorations, but rather interior finish. Section 19.3.3.2 of the 2012 LSC requires interior finish to meet section 10.2 and limits them to Class A or Class B materials. 

Read the complete answer. 

 



March 3, 2016


Topic Area: Safety


Recent Posts

Hospital Evacuation Highlights Importance of Emergency Preparedness

Berger Hospital was evacuated after smoke was discovered in the basement.


Building a Culture of Infection Prevention

Investing in infection prevention can benefit healthcare organizations and patient outcomes.


Ground Broken on Sanford Health Fargo's Peltier Lodge

The 28,400-square-foot facility will feature spaces to support patients and loved ones during treatment and throughout their outpatient care and monitoring.


Arkansas Urology Associates Experiences Data Security Incident

The incident occurred in March.


The Role of Facilities Managers in Healthcare Design

Jiayin Li discusses the way in-house facilities teams can help shape the design of key spaces.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.