Q&A on interior finish

In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about interior finish


In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about interior finish.

Q: I would like to know the 2012 Life Safety Code (LSC) requirements for an audio testing room in a high-rise hospital. The floor, wall and ceilings are covered with cloth materials similar to carpet. The room has been protected by a smoke detector and sprinkler.

A: The wall coverings would not be considered decorations, but rather interior finish. Section 19.3.3.2 of the 2012 LSC requires interior finish to meet section 10.2 and limits them to Class A or Class B materials. 

Read the complete answer. 

 



March 3, 2016


Topic Area: Safety


Recent Posts

Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


Jackson Hospital Falls Victim to Third-Party Cybersecurity Incident

Jackson Hospital has no evidence that any personal information has been or will be used for identity theft as a direct result of this incident.


Making Healthcare Lighting Retrofits Work

Effective operational planning determines whether a retrofit project improves a facility or creates new problems.


Stadium Design is Reshaping Healthcare Facilities

Hospitals are turning to the sports industry for innovative ways to support healing and improve the patient experience.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.