Q&A on interior finish

In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about interior finish


In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about interior finish.

Q: I would like to know the 2012 Life Safety Code (LSC) requirements for an audio testing room in a high-rise hospital. The floor, wall and ceilings are covered with cloth materials similar to carpet. The room has been protected by a smoke detector and sprinkler.

A: The wall coverings would not be considered decorations, but rather interior finish. Section 19.3.3.2 of the 2012 LSC requires interior finish to meet section 10.2 and limits them to Class A or Class B materials. 

Read the complete answer. 

 



March 3, 2016


Topic Area: Safety


Recent Posts

Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


The Children's Center of Hamden Reports Data Security Incident

The incident was detected on December 28, 2024.


Designing for Senior Care Communities Means Designing for Everyone

No spaces can be designed for just one person, designers need to think about everyone who will occupy the space.


Harlem Hospital Legionnaires' Outbreak Highlights Cooling Tower Risks

Seven deaths linked to the cooling towers underscore the need for stricter water system monitoring and preventive maintenance in healthcare settings.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.