Q: We are presently undergoing our three-year licensure inspection by the Dept. of Health. One of the inspectors asked to see our air change records for the morgue. We have never completed air changes for the morgue. We use outside air and make sure the exhaust fan is working properly. So, should we be doing air change testing in the morgue? Also, do we need to do air change testing in all clean and soiled utility rooms in the hospital?

A: When your facility was designed and constructed, the HVAC system had to be designed to certain Air Changes per Hour (ACH). Depending when the facility was designed, the designer would use the AIA Guidelines or the FGI Guidelines, or other state or local regulations as appropriate. You need to find out what those design ACH were at the time the facility was designed/constructed, or last renovated in that area.

It is important to understand that you do not have to meet the latest edition of FGI Guidelines; you just have to meet the edition at the time your facility was designed, or last renovated. It is important to also understand that you must comply with state and local regulations at all times.

So, let’s say the morgue was required to have six ACH at the time it was designed. You must maintain that six ACH for the life of the building, or until you renovate; then you would have to comply with new construction ACH for a morgue. The state inspector’s request is valid: How do you know you are maintaining six ACH if you don’t measure it from time to time? How often should you measure the ACH? The codes and standards do not say, so do a risk assessment and determine what is a valid number. Usually once per year is sufficient as long as you have historical data that shows the ACH rate was always in compliance.

You need to start measuring ACH rates in all areas where there was a design requirement for ACH.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



July 17, 2019


Topic Area: HVAC


Recent Posts

Grounding Healthcare Spaces in Hospitality Principles

Thoughtful design can establish the calm of a spa and the restorative feeling of a resort in healthcare spaces, bringing benefits for patients and care providers.


UC Davis Health Selects Rudolph and Sletten for Central Utility Plant Expansion

Work is already underway with substantial completion anticipated in the fall of 2027.


Cape Cod Healthcare Opens Upper 2 Floors of Edwin Barbey Patient Care Pavilion

The first two floors opened for patients in May 2025 and house the Davenport-Mugar Cancer Center.


Building Sustainable Healthcare for an Aging Population

Traditional responses — building more primary and secondary care facilities — are no longer sustainable.


Froedtert ThedaCare Announces Opening of ThedaCare Medical Center-Oshkosh

The organization broke ground on the health campus in March 2024.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.