Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Air changes in the morgue

Brad Keyes discusses regulations for air changes in the morgue

By Brad Keyes / Special to Healthcare Facilities Today


Q: We are presently undergoing our three-year licensure inspection by the Dept. of Health. One of the inspectors asked to see our air change records for the morgue. We have never completed air changes for the morgue. We use outside air and make sure the exhaust fan is working properly. So, should we be doing air change testing in the morgue? Also, do we need to do air change testing in all clean and soiled utility rooms in the hospital?

A: When your facility was designed and constructed, the HVAC system had to be designed to certain Air Changes per Hour (ACH). Depending when the facility was designed, the designer would use the AIA Guidelines or the FGI Guidelines, or other state or local regulations as appropriate. You need to find out what those design ACH were at the time the facility was designed/constructed, or last renovated in that area.

It is important to understand that you do not have to meet the latest edition of FGI Guidelines; you just have to meet the edition at the time your facility was designed, or last renovated. It is important to also understand that you must comply with state and local regulations at all times.

So, let’s say the morgue was required to have six ACH at the time it was designed. You must maintain that six ACH for the life of the building, or until you renovate; then you would have to comply with new construction ACH for a morgue. The state inspector’s request is valid: How do you know you are maintaining six ACH if you don’t measure it from time to time? How often should you measure the ACH? The codes and standards do not say, so do a risk assessment and determine what is a valid number. Usually once per year is sufficient as long as you have historical data that shows the ACH rate was always in compliance.

You need to start measuring ACH rates in all areas where there was a design requirement for ACH.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



July 17, 2019


Topic Area: HVAC


Recent Posts

Flexible Design Strategies Help OhioHealth Maximize Clinical Space

Doing more with less was key to the renovated facility’s design.


New Bass Center for Childhood Cancer and Blood Diseases Opens

The new space not only offers more exam rooms but also features 15 private infusion bays to allow privacy for all patients and their caregivers during treatment.


Encompass Health Rehabilitation Hospital of Daytona Beach Opens

Hospital amenities include all private patient rooms, a spacious therapy gym featuring advanced rehabilitation technologies, an activities of daily living suite and more.


What Healthcare Facilities Can Learn from a $49 Million Window Failure

A major window system failure at the University of Iowa’s Children’s Hospital sparked a costly replacement project – and a $49.4 million arbitration win.


Family Care Center Opens Newest Clinic in Memphis

It has expanded to offer comprehensive mental health services for all ages in Germantown neighborhood of Memphis.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.