Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Annunciator panels

Brad Keyes discusses regulations for annunciator panels

By Brad Keyes / Special to Healthcare Facilities Today


Q: We are currently in the process of installing a new fire alarm system in our hospital. The old system has an annunciator panel at every nurse station and multiple locations throughout the building. Is it required by code to have annunciator panels at every nurse station? Our telephone operators monitor the fire alarm panel 24/7.

A: Section 9.6.3.6.3 of the 2012 LSC says only the attendants and other personnel required to evacuate occupants from a zone, area, floor, or building shall be required to be notified. The notification is required to include means to readily identify the zone, area, floor, or building in need of evacuation.

 If the facility has patient rooms with smoke detectors and one of those activates, the nursing staff of the affected area is integral to the response, so the ‘readily’ portion of that requirement may mean an annunciator at the nurse station if the facility uses a coded system.  Most nurses aren’t familiar with what the codes mean, so the code may not provide the best response to an emergency situation in patient areas. That doesn’t mean coded systems have to have annunciators at nurse stations, but the intent of notification is to safeguard immobile patients & response time is critical.  Again, this mostly applies to healthcare facilities with detectors in patient rooms.  If that’s the case here, they should review what their response is without nurse station annunciation and determine whether that provides the proper response. 

NOTE: Gene Rowe of Affiliated Fire Systems provided the answer to this question.  

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



December 4, 2019


Topic Area: Safety


Recent Posts

Cleanliness in Hospitals: Clinical Priority and Community Perception

EVS managers and communities value cleanliness for complementary reasons: managers for safety and compliance, communities for trust and comfort.


Dana-Farber Receives $50M Gift for Planned Cancer Hospital

A $50 million grant from the Yawkey Foundation will support construction of Dana-Farber Cancer Institute’s planned 450,000-square-foot cancer hospital.


Clarinda Regional Health Center Reports Data Security Incident

On or around December 15, 2025, Clarinda learned that certain data within its network may have been accessed without authorization.


Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.