Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Corridor transaction window

Brad Keyes discusses regulations for corridor transaction windows

By Brad Keyes / Special to Healthcare Facilities Today


Q: Do transaction windows in a smoke-resistive non-rated corridor wall in a healthcare occupancy need be self-closing?

A: It depends on what space the window is open to. Section 19.3.6.1 of the 2012 LSC says corridors (in healthcare occupancies) must be separated from all other areas by partitions (either smoke resistant or ½-hour fire-rated, depending on the sprinkler protection), unless it complies with one of the following exceptions to be open to the corridor:

1. Spaces unlimited in size, provided:

• The smoke compartment is fully protected with quick-response sprinklers;

• The space is not used for patient sleeping rooms, treatment rooms, or hazardous areas;

• The corridor is protected with smoke detectors, or the smoke compartment is protected with QR sprinklers;

• The space is protected with smoke detectors, or the space is arranged to allow direct supervision by staff;

• The space does not obstruct access to required exits.

2. Spaces unlimited in size, provided:

• The space is not used for patient sleeping rooms, treatment rooms, or hazardous areas;

• The space and the corridor are protected with smoke detectors;

• The space is protected with sprinklers, or the furnishings and furniture, in combination with all other combustibles within the area, are of such minimal quantity and arrangement that a fully developed fire is unlikely to occur;

• The space does not obstruct access to required exits.

The presumption here is the space is not a waiting area, a nurse station, a Gift shop, a limited-care facility, a kitchen, or a group meeting room, so those exceptions do not apply.

So, you say it is a transaction window… Let’s assume it is a sliding window to an accounting area where patients can make payments. If the accounting area meets exceptions #1 or #2, then a sliding window that does not resist the passage of smoke or positively latch is permitted. However, you will need to identify on the Life Safety drawings that the corridor wall no longer exists where the sliding window is located but is now located around the back of the accounting area. That means the walls in the back of the accounting area now becomes the corridor walls, and they must meet the requirements for corridor walls (19.2.6.2) and any openings must meet the requirements for corridor doors (19.3.6.3).

It might just be easier to make the sliding window smoke resistant and positive latching. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



February 13, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

Making Healthcare Lighting Retrofits Work

Effective operational planning determines whether a retrofit project improves a facility or creates new problems.


Harris Health to Build New Freestanding Cancer Center

The center is planned to open in 2029, following the opening of the new O'Quinn Hospital along the North Loop at Lockwood.


Inland Empire Health Plan Opens Expanded San Bernardino Community Wellness Center

The new 33,000-square-foot center is nearly three times the size of the original location off Second Street.


Rethinking Parking Lot Design at Irvine Heritage Medical Plaza

A new solar installation shows how healthcare facilities can improve parking amenities while boosting energy savings


Repurposing Healthcare Spaces: 5 Critical Questions

Done well, converting existing spaces can trim upfront project costs by up to 40 percent, compared with ground-up construction


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.