Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Suite doors

Brad Keyes discusses regulations for suite doors

By Brad Keyes / Special to Healthcare Facilities Today


Q: Does the 2012 edition of the Life Safety Code permit existing suite doors opening into the corridor to be compliant if they do not latch shut? We have different interpretations of 19.2.5.7.1.2.

A: No. Corridor entrance doors to suites must latch. Section 19.3.6.3.5 requires all corridor doors to latch. CMS does not allow the exception for a device that holds the door closed with 5 lbs. of force. Since a suite is nothing more than a room, the barrier that separates the suite from the corridor must meet the conditions for corridor walls, which means the door must latch. The provision in 19.2.5.7.1.2 (2) is there to allow existing suites to have smoke resistant walls when fire-rated barriers are required by the corridor walls.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



June 19, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

Extreme Weather: The Maintenance-Resilience Link

Extreme heat serves as stress test of the resilience of utility systems that provide power, cooling and life safety functions.


Encompass Health Lower Providence Opens in Pennsylvania

The 50-bed inpatient rehabilitation hospital is the company's 11th location in Pennsylvania.


Intermountain Health Acquires Fairbourne Building for Healthcare Hub and Medical Campus Conversion

Construction on the interior of the building is underway with the city and Intermountain working closely together on the campus.


Cooling Towers at NYC Health + Hospitals/Lincoln Test Positive for Legionella

Hospital among the positive tests at 10 cooling towers in South Bronx.


Prefabricated Wall Panels Accelerate UCF Lake Nona Medical Center Construction

Case study: StoPanel exterior wall systems helped Wal-Mark Contracting meet strict Florida wind-load requirements and complete 136 panels in just 11 days.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.