Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Corridor transaction window

Brad Keyes discusses regulations for corridor transaction windows

By Brad Keyes / Special to Healthcare Facilities Today


Q: Do transaction windows in a smoke-resistive non-rated corridor wall in a healthcare occupancy need be self-closing?

A: It depends on what space the window is open to. Section 19.3.6.1 of the 2012 LSC says corridors (in healthcare occupancies) must be separated from all other areas by partitions (either smoke resistant or ½-hour fire-rated, depending on the sprinkler protection), unless it complies with one of the following exceptions to be open to the corridor:

1. Spaces unlimited in size, provided:

• The smoke compartment is fully protected with quick-response sprinklers;

• The space is not used for patient sleeping rooms, treatment rooms, or hazardous areas;

• The corridor is protected with smoke detectors, or the smoke compartment is protected with QR sprinklers;

• The space is protected with smoke detectors, or the space is arranged to allow direct supervision by staff;

• The space does not obstruct access to required exits.

2. Spaces unlimited in size, provided:

• The space is not used for patient sleeping rooms, treatment rooms, or hazardous areas;

• The space and the corridor are protected with smoke detectors;

• The space is protected with sprinklers, or the furnishings and furniture, in combination with all other combustibles within the area, are of such minimal quantity and arrangement that a fully developed fire is unlikely to occur;

• The space does not obstruct access to required exits.

The presumption here is the space is not a waiting area, a nurse station, a Gift shop, a limited-care facility, a kitchen, or a group meeting room, so those exceptions do not apply.

So, you say it is a transaction window… Let’s assume it is a sliding window to an accounting area where patients can make payments. If the accounting area meets exceptions #1 or #2, then a sliding window that does not resist the passage of smoke or positively latch is permitted. However, you will need to identify on the Life Safety drawings that the corridor wall no longer exists where the sliding window is located but is now located around the back of the accounting area. That means the walls in the back of the accounting area now becomes the corridor walls, and they must meet the requirements for corridor walls (19.2.6.2) and any openings must meet the requirements for corridor doors (19.3.6.3).

It might just be easier to make the sliding window smoke resistant and positive latching. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



February 13, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

Upward Mobility: Market Forces Drive Hospitals Higher

Healthcare facilities nationwide are navigating challenges and opportunities presented by expanding their reach into the sky.


Georgia Hospital Bomb Hoaxes Highlight Need for Healthcare–Police Partnerships

Proactive planning and close collaboration with law enforcement help healthcare facilities maintain safety and continuity during false threats.


MUSC Health Celebrates Groundbreaking for Nexton Hospital and Ambulatory Cancer Facility

The Nexton cancer facility is expected to open in summer 2027, and the Nexton hospital in summer 2028.


Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.