Regulations, Codes & Standards Q&A: Sprinkler obstructions

Brad Keyes discusses regulations for vertical clear space

By Brad Keyes / Special to Healthcare Facilities Today


Q: My question is in regard to NFPA 13 sprinkler obstruction compliance...We want to install some surveillance monitors in our security office along a wall. How much vertical clear space is required between the monitors to the ceiling, if the monitors will be 30 inches away, horizontally from the sprinkler head?

A: Those monitors may extend vertically up to the ceiling as long as they are not directly underneath a sprinkler head, and they are attached to the wall. You said they were 30 inches away horizontally from the sprinklers, so you should be okay.  

Section A.8.6.6 of NFPA 13-2010 says the following:

“The 18 in. (457 mm) dimension is not intended to limit the height of shelving on a wall or shelving against a wall in accordance with 8.6.6, 8.7.6, 8.8.6, and Section 8.9. Where shelving is installed on a wall and is not directly below sprinklers, the shelves, including storage thereon, can extend above the level of a plane located 18 in. (457 mm) below ceiling sprinkler deflectors. Shelving, and any storage thereon, directly below the sprinklers cannot extend above a plane located 18 in. (457 mm) below the ceiling sprinkler deflectors.”

While the monitor may not be shelves, the concept is the same.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



October 10, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Preparing Healthcare Facilities for Wildfire Air Quality Events

Wildfire smoke puts pressure on mechanical systems already working hard to maintain controlled indoor environments.


UW Health Set to Open Expansion at East Madison Hospital

The $140 million project adds 120,000 square feet to the hospital, expanding its footprint to roughly 620,000 square feet.


Central Ohio Primary Care Physicians Falls Victim to Cyberattack

While the full extent of the incident is still under review, our initial investigation discovered that there are approximately 1.4 million individuals impacted.


The Role of Biophilic Design in Healthcare Facilities

Nature-inspired design can support staff well-being and create more welcoming, human-centered healthcare environments.


TriStar Centennial Medical Center Invests $90M in Women, Children's Hospital Expansions

The multi-year project will bring significant improvements to both hospitals.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.