Regulations, Codes & Standards Q&A: Sprinkler obstructions

Brad Keyes discusses regulations for vertical clear space

By Brad Keyes / Special to Healthcare Facilities Today


Q: My question is in regard to NFPA 13 sprinkler obstruction compliance...We want to install some surveillance monitors in our security office along a wall. How much vertical clear space is required between the monitors to the ceiling, if the monitors will be 30 inches away, horizontally from the sprinkler head?

A: Those monitors may extend vertically up to the ceiling as long as they are not directly underneath a sprinkler head, and they are attached to the wall. You said they were 30 inches away horizontally from the sprinklers, so you should be okay.  

Section A.8.6.6 of NFPA 13-2010 says the following:

“The 18 in. (457 mm) dimension is not intended to limit the height of shelving on a wall or shelving against a wall in accordance with 8.6.6, 8.7.6, 8.8.6, and Section 8.9. Where shelving is installed on a wall and is not directly below sprinklers, the shelves, including storage thereon, can extend above the level of a plane located 18 in. (457 mm) below ceiling sprinkler deflectors. Shelving, and any storage thereon, directly below the sprinklers cannot extend above a plane located 18 in. (457 mm) below the ceiling sprinkler deflectors.”

While the monitor may not be shelves, the concept is the same.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



October 10, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Cleanliness in Hospitals: Clinical Priority and Community Perception

EVS managers and communities value cleanliness for complementary reasons: managers for safety and compliance, communities for trust and comfort.


Dana-Farber Receives $50M Gift for Planned Cancer Hospital

A $50 million grant from the Yawkey Foundation will support construction of Dana-Farber Cancer Institute’s planned 450,000-square-foot cancer hospital.


Clarinda Regional Health Center Reports Data Security Incident

On or around December 15, 2025, Clarinda learned that certain data within its network may have been accessed without authorization.


Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.