Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Sprinkler obstructions

By Brad Keyes / Special to Healthcare Facilities Today
October 10, 2018

Q: My question is in regard to NFPA 13 sprinkler obstruction compliance...We want to install some surveillance monitors in our security office along a wall. How much vertical clear space is required between the monitors to the ceiling, if the monitors will be 30 inches away, horizontally from the sprinkler head?

A: Those monitors may extend vertically up to the ceiling as long as they are not directly underneath a sprinkler head, and they are attached to the wall. You said they were 30 inches away horizontally from the sprinklers, so you should be okay.  

Section A.8.6.6 of NFPA 13-2010 says the following:

“The 18 in. (457 mm) dimension is not intended to limit the height of shelving on a wall or shelving against a wall in accordance with 8.6.6, 8.7.6, 8.8.6, and Section 8.9. Where shelving is installed on a wall and is not directly below sprinklers, the shelves, including storage thereon, can extend above the level of a plane located 18 in. (457 mm) below ceiling sprinkler deflectors. Shelving, and any storage thereon, directly below the sprinklers cannot extend above a plane located 18 in. (457 mm) below the ceiling sprinkler deflectors.”

While the monitor may not be shelves, the concept is the same.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 

See the latest posts on our homepage


Share

Topic Area: Regulations, Codes & Standards


Recent Posts
Recent Posts
Focus: Facility Design

Designing for introverts and extroverts


Private spaces energize introverts and social spaces energize extroverts, according to an article on the Healthcare Design website

2/15/2019

Blog

A crash course in GRC for the healthcare industry


Healthcare facilities must take the time to ensure that all employees are educated on governance, risk and compliance (GRC) when it comes to information security

2/15/2019

Focus: Facility Design

Balancing sustainable design and efficiency


Upgrades to green building standards have provided a solid framework

2/15/2019

Health system energy investments support carbon goal


Kaiser Permanente purchases wind, solar and battery energy

2/15/2019

Focus: Plumbing

Study says removing sinks from ICU cuts bacterial colonization


'Water-free' patient care can reduce the number of ICU patients colonized with gram-negative bacteria

2/15/2019





Post Comment




FREE
NEWSLETTER

News & Updates • Webcast Alerts • Building Technologies

All fields are required.