Inspecting, Testing, And Maintaining Fire Alarm Systems

Refer to Chapter 14 of NFPA 72 to understand minimum levels of performance for fire alarm systems


Fire alarm systems play an important role in the ability of institutional and commercial facilities to provide early warning to and safely evacuate occupants during a fire emergency. The fire alarm system must operate and function properly, but it is difficult to tell if a system is fully operational just by looking at it, according to an article from Facility Maintenance decisions on the FacilityNet website.

Fire alarm systems are mostly made of electronics that degrade over time and can compromise system readiness, so proper maintenance, inspection and testing can ensure a system works as designed.

These steps also are required by local fire code, such as the International Fire Code 2018, 907.8: “The maintenance and testing schedules and procedures for fire alarm and fire detection systems shall be in accordance with NFPA 72.” NFPA 72 National Fire Alarm and Signaling Code covers the application, installation, location, performance, inspection, testing and maintenance of fire alarm systems.

Maintenance and engineering managers need to ensure their front-line technicians follow the code when maintaining fire alarm systems. Proper testing, inspection and maintenance also ensure systems remain in the best possible working condition and reduce costs by preventing repairs and false alarms.

Inspection, testing and maintenance requirements for fire alarm systems can be found in Chapter 14 of the NFPA 72. The code establishes minimum required levels of performance, but it does not establish the only methods by which departments can meet these requirements. In other words, the code allows for requirements from other sources that exceed those in Chapter 14.

Read the full article on FacilitiesNet.

 

 

 



August 18, 2020


Topic Area: Safety


Recent Posts

Seeking Standards for Microbial Loads in Healthcare Facilities

Why is there no binding standard for the acceptable microbial load on surfaces or in the air in hospitals?


UCR Health Unveils Plans for Major Expansion

The vision for the site will include an outpatient diagnostic center and possible future expansion.


High-Performance Windows Support Safety at UW Medicine's New Behavioral Health Center

Case study: Engineered for strength, quiet and daylight, the chosen windows help create a safe, calming and energy-efficient environment for patients and providers.


Central Maine Healthcare Dealing with IT System Outage

The organization identified unusual activity within their computer software, prompting them to secure and shut off all IT systems.


Kaiser Permanente Opens Newly Expanded Everett Medical Center

The facility offers primary care and pediatric care and has specialty care departments.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.