Are Smoke Alarms Necessary In Sleeping Rooms?

It all depends on the facility type and situation


Question: Are smoke alarms in bedrooms necessary in a grandfathered situation, such as:

  • Non-sprinkled healthcare facility, except domestic water fed sprinklers in mechanical, boiler and storage rooms
  • Will house ambulatory, overnight drug rehab patients 
  • With unlocked doors to the outside and if needed. 
  • Do they need to be tied in to the pre-existing fire alarm system that is already in the hallways?

Answer from Brad Keyes: The question doesn’t state if it’s a hospital or a nursing home or if it’s new construction or existing construction. Also, the writer did not clarify if the sleep rooms are for staff or patients. All of that does make a difference.

If you are a hospital…

Then there is no requirement to have smoke detectors (or smoke alarms) in patient sleeping rooms. However, there is a requirement to have single station smoke alarms in staff sleeping rooms. Section 9.6.2.10.1.4 of the 2012 LSC does permit a smoke detector connected to the building fire alarm system in lieu of a single station smoke alarm, but it would still need to have the capability to notify the occupants in the case of an alarm.

If you are an existing nursing home…

Section 19.3.4.5.1 of the 2012 LSC does require smoke detectors in corridors unless there are smoke detectors in the patient’s sleeping rooms, or unless the smoke compartment is fully protected with sprinklers (which is required by CMS at this time). 

If you are a new construction nursing home…

Section 18.3.4.5.1 of the 2012 LSC does require smoke detectors in corridors unless there are smoke detectors in the patient’s sleeping rooms, or unless the patient room doors are equipped with automatic closing devices with integral smoke detectors on the room side and the smoke detectors provide occupant notification. 

There is no “grandfathering” in the Life Safety Code. There are “existing” occupancy chapters that all healthcare facilities constructed prior to July 5, 2016, are expected to comply with, but it is not the same as saying it is “grandfathered.” The existing occupancy chapter for healthcare does change from edition to edition. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 25, 2020



Recent Posts

What Does Light Daily Cleaning Miss in Patient Rooms?

Most environmental services workers still clean as if they are wiping dust off a countertop, not disrupting a living, structured community.


Smart Lighting Overhaul Boosts Efficiency, Diagnostics and Wellness at Bryan Health

Case study: LED upgrade and advanced controls across Bryan Health campuses cut lighting energy use by 57 percent while enhancing patient care and staff productivity.


AdventHealth Opens New Freestanding ER in Florida

The approximately 13,700-square-foot emergency room features 12 patient rooms, respiratory therapy services, diagnostic imaging including CT scans, X-ray and ultrasound.


Dirty Floors: How Pathogens Can Accumulate and Spread Underfoot

Studies show that healthcare floors are covered in bacteria and can quickly spread throughout patient rooms. 


WellSpan Health Opens Its Newberry Hospital in Pennsylvania

This marks the opening of its 10th hospital in the region spanning Central Pennsylvania and Northern Maryland.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.