Fire Safety Q&A: Where To Place Fire Extinguishers

Know the clearance radius before mounting fire extinguishers


Question: Do fire extinguishers have a specific clearance radius from where they are mounted or located?

Answer from Brad Keyes: NFPA 10-2010 says this about placement of fire extinguishers:

  • 6.1.3.1 Fire extinguishers shall be conspicuously located where they are readily accessible and immediately available in the event of fire.

  • 6.1.3.2 Fire extinguishers shall be located along normal paths of travel, including exits from areas.

  • 6.1.3.3.1 Fire extinguishers shall not be obstructed or obscured from view.

  • 6.1.3.3.2 In large rooms and in certain locations where visual obstructions cannot be completely avoided, means shall be provided to indicate the extinguisher location.

 

So, they must be visible, readily accessible and immediately available. Most authorities having jurisdiction (AHJ) will expect at least 36-inches clearance in front of the extinguisher as long as it is still visible. They “borrow” this 36-inch clearance measurement from NFPA 70-2011, Article 110.26 for electrical control panels. As an authority having jurisdiction (AHJ) they are permitted by section 4.6.1.1 of the 2012 Life Safety Code to make this interpretation.



Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 18, 2020



Recent Posts

Skills Gap Remains Wide in Facilities Management

Many candidates lack the skills that are needed to be a facilities manager.


Making Healthcare Lighting Retrofits Work

Effective operational planning determines whether a retrofit project improves a facility or creates new problems.


Harris Health to Build New Freestanding Cancer Center

The center is planned to open in 2029, following the opening of the new O'Quinn Hospital along the North Loop at Lockwood.


Inland Empire Health Plan Opens Expanded San Bernardino Community Wellness Center

The new 33,000-square-foot center is nearly three times the size of the original location off Second Street.


Rethinking Parking Lot Design at Irvine Heritage Medical Plaza

A new solar installation shows how healthcare facilities can improve parking amenities while boosting energy savings


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.