Question: Do fire extinguishers have a specific clearance radius from where they are mounted or located?

Answer from Brad Keyes: NFPA 10-2010 says this about placement of fire extinguishers:

  • 6.1.3.1 Fire extinguishers shall be conspicuously located where they are readily accessible and immediately available in the event of fire.

  • 6.1.3.2 Fire extinguishers shall be located along normal paths of travel, including exits from areas.

  • 6.1.3.3.1 Fire extinguishers shall not be obstructed or obscured from view.

  • 6.1.3.3.2 In large rooms and in certain locations where visual obstructions cannot be completely avoided, means shall be provided to indicate the extinguisher location.

 

So, they must be visible, readily accessible and immediately available. Most authorities having jurisdiction (AHJ) will expect at least 36-inches clearance in front of the extinguisher as long as it is still visible. They “borrow” this 36-inch clearance measurement from NFPA 70-2011, Article 110.26 for electrical control panels. As an authority having jurisdiction (AHJ) they are permitted by section 4.6.1.1 of the 2012 Life Safety Code to make this interpretation.



Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



November 18, 2020



Recent Posts

Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


The Children's Center of Hamden Reports Data Security Incident

The incident was detected on December 28, 2024.


Designing for Senior Care Communities Means Designing for Everyone

No spaces can be designed for just one person, designers need to think about everyone who will occupy the space.


Harlem Hospital Legionnaires' Outbreak Highlights Cooling Tower Risks

Seven deaths linked to the cooling towers underscore the need for stricter water system monitoring and preventive maintenance in healthcare settings.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.