Life Safety Q&A: Door to compressed gas storage rooms

Brad Keyes discusses the doors to compressed gas storage rooms

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have an oxygen/med gas storage room that is attached to the hospital, and can only gain access to the room by way of the exterior of building. Does the room have to have a fire-rated door assembly?

A: Well… that depends. If the storage room contains 3,000 cubic feet or more of compressed medical gases, and the room is located indoors, then the room must be constructed with 1-hour fire-rated construction and the door to the room is required to be 1-hour (not ¾-hour) fire rated as well (see 5.1.3.3.2(4) of NFPA 99-2012).

However, the intent of 5.1.3.3.2 is to separate the compressed gas storage room from the rest of the facility by requiring 1-hour fire rated barriers, and if the door opening to the storage room opens into the facility, one could easily understand why a fire-rated door is required. However, if the door to the storage room opens to the outdoors (i.e. receiving dock) then one could make a point that the doors is not required to be fire-rated, because there is no separation between the storage room and the rest of the facility at that point.

But the problem is, NFPA 99-2012 section 5.1.3.3.2 does not say that and does not appear to have any exception for a door to the storage room that opens to the outdoors. I think a rational, smart, understanding surveyor would agree with that point and not cite you for not having a fire-rated door that opens to the outdoors.

But will you always have a rational, smart, and understanding surveyor?

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



October 4, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

The Hidden Risks of QAC Disinfectants in Healthcare Facilities

Quaternary ammonium compounds are a popular disinfectant choice, but they may be causing more harm than good. A review outlines the problems with QACs and offers a solution.


Sprinkler Compliance: Navigating Code Mandates, Renovation Triggers and Patient Safety

As CMS deadlines approach and renovation projects accelerate, healthcare facility managers must understand how NFPA 101, state fire codes and sprinkler design strategies intersect.


Baptist Health Acquires South Arkansas Regional Hospital

Now operating as Baptist Health Medical Center-El Dorado, the 151-bed facility is the 13th hospital in the Baptist Health system.


Wider View: Planning LED Upgrades Across a Healthcare Portfolio

Upgrade planning has to start with a systemwide, portfolio approach rather than a site-by-site mindset.


Cone Health Plans Hospital in Forsyth County of North Carolina

The 198,593 square-foot facility will be in southeast Forsyth County.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.