Focus: Fire-Life Safety / Column

Life Safety Q&A: Fire-rated door assemblies

Brad Keyes discusses fire-rated door assemblies

By Brad Keyes / Special to Healthcare Facilities Today


Q: You have stated in previous Q&As that all fire-rated door assemblies must be tested and inspected. I don’t think that is true on fire-rated door assemblies that are not located in a fire-rated barrier. I was under the impression that the hospital’s current Life Safety drawings would be the determining factor on what barriers the hospital was responsible for maintaining. For example, if the building had rated doors on a wall that was not denoted as a fire rated barrier on the LS drawings, one could justify why there were not maintained. I run into the installation of unnecessary rated doors in many facilities, both old and new.

A: You make an interesting case. However, the Life Safety Code always trumps everything else, and in this case it would trump the hospital’s LS drawings. According to 7.2.1.15.2 of the 2012 LSC, it clearly says all fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80. There is no exception for fire-rated door assemblies that are not located in a fire-rated barrier.

My advice is to remove the fire-rated label if the facility is sure the barrier is not a fire-rated barrier.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



September 13, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

On the Lookout: The Software Supply Chain as a Healthcare Cyberattack Vector

Staying watchful of third-party software vendors and their activities is critical for healthcare cybersecurity.


Hackensack Meridian Health & Wellness Center at Clifton Opens

The Clifton center expands health care access in Passaic County by reducing barriers such as travel and wait times.


Suffolk Breaks Ground on Expansion of White Plains Hospital

The 10-story, approximately 500,000-square-foot expansion is slated to open in 2028.


EVS Leadership Culture Critical in Preventing Hospital-Acquired Sepsis

Cleaning is an essential yet complex component for the prevention of HAI-induced sepsis.


Man Dies by Suicide in Emergency Department Waiting Room at Kansas Hospital

No staff or patients were harmed, and the man was alone in the waiting area when he shot himself.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.