Life Safety Q&A: Fire-rated door assemblies

Brad Keyes discusses fire-rated door assemblies

By Brad Keyes / Special to Healthcare Facilities Today


Q: You have stated in previous Q&As that all fire-rated door assemblies must be tested and inspected. I don’t think that is true on fire-rated door assemblies that are not located in a fire-rated barrier. I was under the impression that the hospital’s current Life Safety drawings would be the determining factor on what barriers the hospital was responsible for maintaining. For example, if the building had rated doors on a wall that was not denoted as a fire rated barrier on the LS drawings, one could justify why there were not maintained. I run into the installation of unnecessary rated doors in many facilities, both old and new.

A: You make an interesting case. However, the Life Safety Code always trumps everything else, and in this case it would trump the hospital’s LS drawings. According to 7.2.1.15.2 of the 2012 LSC, it clearly says all fire-rated door assemblies shall be inspected and tested in accordance with NFPA 80. There is no exception for fire-rated door assemblies that are not located in a fire-rated barrier.

My advice is to remove the fire-rated label if the facility is sure the barrier is not a fire-rated barrier.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



September 13, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Designing for Distraction: Benefits for Children, Families

Designers who can incorporate distractions into pediatric healthcare facilities can help children and families successfully navigate healthcare journeys.


Staffing and Consolidation Reshape Outpatient Facility Strategies

Labor shortages and health system consolidation are driving new approaches to outpatient facility planning.


Adams Health Network Falls Victim to Phishing Attack

Adams Health Network does not have any evidence that the attacker was seeking patient information.


Ventilation and Filtering for Infection ControlĀ 

Poor IAQ can be deadly in healthcare facilities, so maintaining proper air conditioning and filter systems is key in controlling the spread of infection.


ChristianaCare Opens Aston Campus Neighborhood Hospital

The hospital is expected to care for approximately 15,000 patients each year.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.