Column

Q&A: Creating separated occupancies

Brad Keyes discusses creating separated occupancies

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have a three-story hospital and I would like to have a mixed occupancy classifications for different floors. The basement floor is for support — no patients are ever on this floor for any reason. The top floor is administration. Patients are occasionally on this floor if they are being transported to the adjacent hospital — always in the company of nursing staff and only for 1-2 minutes at a time during transport. No treatments and no overnight stays on this floor. Can I declare the main floor to be healthcare occupancy and the other two floors to be business occupancy? If so, what are the proper steps to make this happen; do I need to involve an architect, do the life safety plans need to be retitled, can I make this decision myself or do I need approval of some sort?

A: You should not make this decision by yourself. You need to employ an architect who has healthcare experience and a good working knowledge of the Life Safety Code. 

You did not mention what your facility construction type is (according to NFAP 220). Take a look at 19.1.6.1 of the 2012 LSC… there is a Table that lists all of the approved constructions types for existing hospitals.  It is important to know because you will need a 2-hour fire rated barrier between the floors where you want separated occupancies in your facility. 

It appears you should not have any issues in making the lower level a business occupancy, and there may be some possibility for the upper level as well. But the experienced architect needs to conduct a field review to ensure exiting, construction type and other factors are correct to allow separated occupancies in your facility. 

Once the review has determined you can make these changes, then your Life Safety drawings need to be updated and your Statement of Conditions needs to be updated (if you’re Joint Commission accredited) and perhaps your state or local AHJ may want to review this change as well.  

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



August 31, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Mature Dry Surface Biofilm Presents a Problem for Candida Auris

Multiple methods are described in the literature, but no consensus has been reached for disinfection efficacy tests against biofilms.


Sutter Health's Arden Care Center Officially Opens

With an adaptive reuse of an underutilized office building, the 70,000 square-foot facility was renovated to meet current healthcare standards.


Insight Hospital and Medical Center Falls to Data Breach

The investigation determined that an unauthorized individual accessed the network between August 22, 2025, and September 11, 2025.


The High Cost of Healthcare Violence

As workplace violence increases, healthcare facilities face mounting financial and operational disruptions- prompting legislative action.


EVS Teams Can Improve Patient Experience in Emergency Departments

A report confirmed that cleanliness of the ED was the third most impactful element on patient experience surveys.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.