Q&A: Fire alarm audible devices in physician sleep rooms

Brad Keyes says monthly load tests are required for emergency power generators at ambulatory healthcare occupancies

By Brad Keyes / Special to Healthcare Facilities Today


Q: We have audible notification devices for the fire alarm system installed in our physician sleep rooms. We have a physician requesting the one in his area be removed. Are we permitted to remove the audible devices or do we have to have them?

A: Well…. I would certainly remove any audible alarm notification devices from a physician sleeping room, but there are some surveyors who are sticklers for them. Here is the reason why:

A physician sleeping room on a patient unit would be considered a mixed occupancy as the physician sleeping room would have to meet chapter 29 Existing Hotels & Dormitories. Section 29.3.4.5 of the 2012 Life Safety Code requires an approved single-station smoke alarm in every sleeping room. A smoke alarm is different than the typical smoke detector in the hospital. The smoke alarm is required to have an audible device when the smoke alarm is activated it will alert the individual in the room. So, technically, the audible device is required and some surveyors actually require it. 

However, since the sleeping room is in a hospital, most accreditation organizations allow a hospital smoke detector to be installed in the sleeping room in lieu of a smoke alarm since there is staff on duty that would wake any sleeping physicians in the event of a fire. But, not all surveyors and AHJs see it that way and actually require the smoke alarms with audible devices to be installed.

But perhaps the saving grace for you is the smoke alarm in the physician sleeping room is not required to be connected to the building fire alarm system (a smoke detector would be, but not a smoke alarm) so you don’t have to have a building audible notification device in the sleeping room which would activate everytime the fire alarm system is activated. Just have a single-station smoke alarm that has an audible signal installed, which will only activates if the a fire develops in the sleeping room.   

By the way, section 29.3.6.2.2 and 29.3.6.2.3 requires a fire-rated door to that room if the corridor is not sprinklered, and the door needs a closer. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

 

 



July 13, 2016



Recent Posts

Cleanliness in Hospitals: Clinical Priority and Community Perception

EVS managers and communities value cleanliness for complementary reasons: managers for safety and compliance, communities for trust and comfort.


Dana-Farber Receives $50M Gift for Planned Cancer Hospital

A $50 million grant from the Yawkey Foundation will support construction of Dana-Farber Cancer Institute’s planned 450,000-square-foot cancer hospital.


Clarinda Regional Health Center Reports Data Security Incident

On or around December 15, 2025, Clarinda learned that certain data within its network may have been accessed without authorization.


Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.