Focus: Fire-Life Safety / Column

Q&A: Firefighter emergency phones

Brad Keyes discusses firefighter emergency phones

By Brad Keyes / Special to Healthcare Facilities Today


Q: Are firefighter emergency call phones still required in new construction? We have an existing hospital and management is wanting to add a whole new patient tower and the construction company is trying to say they are no longer required. I know the old system was the red phones and the new system is the plug in phones. Can you shed any light on this? 

A: Generally speaking, two-way communications are only required in high rises according to section 11.8.4.2.1 of the 2012 Life Safety Code. However, section 11.8.4.2.2 allows for a fire department radio system installation in lieu of the fire-phones.  Most AHJs utilize these radios so the method of two way communications in a high rise hospital must be coordinated with the fire department.  Most will require the installation of a compatible radio system and will not require the fire-phones. 

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs

Brad's next webcast is scheduled for Dec. 14. He'll be discussing  "New Requirements, New Challenges: The 2012 Life Safety Code."

 



December 7, 2016


Topic Area: Regulations, Codes & Standards


Recent Posts

Cleanliness in Hospitals: Clinical Priority and Community Perception

EVS managers and communities value cleanliness for complementary reasons: managers for safety and compliance, communities for trust and comfort.


Dana-Farber Receives $50M Gift for Planned Cancer Hospital

A $50 million grant from the Yawkey Foundation will support construction of Dana-Farber Cancer Institute’s planned 450,000-square-foot cancer hospital.


Clarinda Regional Health Center Reports Data Security Incident

On or around December 15, 2025, Clarinda learned that certain data within its network may have been accessed without authorization.


Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.