Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Battery-powered emergency lights

Brad Keyes discusses regulations for battery-powered emergency lights

By Brad Keyes / Special to Healthcare Facilities Today


Q: In the standards manual from our accreditation organization it states that every 12 months the critical access hospital either performs a functional test of battery powered lights on the inventory required for egress for a duration of 1½-hours or replaces the batteries and tests 10% of all batteries and records the results. Do we need a written inventory of these lights? If so, can these lights be labeled on a drawing? Or do these need to be listed out in a spreadsheet?

A: First of all.... be careful which edition of the standards you are reading. That accreditation organization changed their standard on this issue in 2018 and eliminated the option of replacing the batteries annually, and only testing 10% of them. The requirement since January 1, 2018 is you must conduct the annual 90-minute test on all of the batteries.

But to answer your question.... Yes… the battery powered emergency lights do need to be listed on an inventory in order to be sure all of them were tested. You may list them on a spread-sheet that identifies them by location and/or asset-tracking number, or you may list them on drawings. Both would be best.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



March 13, 2019


Topic Area: Regulations, Codes & Standards


Recent Posts

The Future of Healthcare Facility Construction Projects

Brian Cowperthwaite highlights the invisible work that impacts everyone who walks through a healthcare facility.


Arnprior Regional Health Upgrades Building Controls to Improve IEQ

Case study: They wanted to improve the hospital facility’s IEQ to support patient care and reduce long-term operating costs.


Next Level Medical Suffers a Data Breach

To date, NLM has no evidence of identity theft or fraud related to this event.


Extreme Weather: The Maintenance-Resilience Link

Extreme heat serves as stress test of the resilience of utility systems that provide power, cooling and life safety functions.


Encompass Health Lower Providence Opens in Pennsylvania

The 50-bed inpatient rehabilitation hospital is the company's 11th location in Pennsylvania.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.