Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Cabinets in a corridor, Part 2

Brad Keyes discusses regulations for cabinets in a corridor

By Brad Keyes / Special to Healthcare Facilities Today


Cabinets in a Corridor – Part 2

Q: Is there a codified requirement for doors in a cabinet mounted in a hospital egress corridor? We have worked on projects when a nurse server; i.e., pass through cabinet, was required by the local AHJ to have positive latching on the cabinet door in order to protect the sanctity of the egress corridor. But when it is just a typical cabinet (non-pass through), is there a danger to the egress corridor if the cabinet doors do not have positive latching?

A: The only code requirements that I can think of are corridor obstruction and projection. A nurse server that has an open pass-through to the patient room from the corridor is required to have a door that meets the requirements of 19.3.6.3 of the 2012 LSC for corridor doors, such as positive latching, 1¾-inch thick solid-bonded wood core, and resisting the passage of smoke, because it needs to separate the corridor from the patient room. I think a typical cabinet that does not have a pass-though would not have to have a door that is positive latching because positive latching is only required when the door is separating a corridor from a room. If there is no pass-through, then there is no need for a positive latching door.   

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



April 11, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Building Sustainable Healthcare for an Aging Population

Traditional responses — building more primary and secondary care facilities — are no longer sustainable.


Froedtert ThedaCare Announces Opening of ThedaCare Medical Center-Oshkosh

The organization broke ground on the health campus in March 2024.


Touchmark Acquires The Hacienda at Georgetown Senior Living Facility

The facility will now be known as Touchmark at Georgetown.


Contaminants Under Foot: A Closer Look at Patient Room Floors

So-called dust bunnies on hospital room floors contain dust particles that turn out to be the major source of the bacteria humans breathe.


Power Outages Largely Driven by Extreme Weather Events

Almost half of power outages in the United States were caused by extreme weather events.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.