Focus: Regulations, Codes & Standards

Regulations, Codes & Standards Q&A: Clean utility rooms

Brad Keyes discusses guidance on clean utility rooms and door closers

By Brad Keyes / Special to Healthcare Facilities Today


Q: What is the guidance on clean utility rooms and door closers? Under 50 square feet no closer is required, but more than 50 square feet a closer is required? Does the clean utility room being located inside a suite make any difference? The normal supplies in there could be considered combustible based on the NFPA definition.

A: You have the 50-square-foot limit correct, but it does not matter if the clean utility room is located in a suite or not. It still must meet section 18/19.3.2.1 for hazardous areas. If it is a new clean utility room, then it must be 1-hour fire-rated and be protected with sprinklers. However, the room may meet an exception found in section 43.7.1.2 (2), regarding rehabilitation.

A change in use of a space in an existing healthcare occupancy does not have to meet new construction requirements for hazardous areas, provided the space does not exceed 250 square feet and the entire building is protected with sprinklers. But the space does have to meet the requirements for hazardous areas for existing conditions, which is 1-hour fire rated construction, or if the room is fully protected with sprinklers, then the door just needs to be self-closing and smoke resistant.  

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



December 13, 2017


Topic Area: Regulations, Codes & Standards


Recent Posts

Cleanliness in Hospitals: Clinical Priority and Community Perception

EVS managers and communities value cleanliness for complementary reasons: managers for safety and compliance, communities for trust and comfort.


Dana-Farber Receives $50M Gift for Planned Cancer Hospital

A $50 million grant from the Yawkey Foundation will support construction of Dana-Farber Cancer Institute’s planned 450,000-square-foot cancer hospital.


Clarinda Regional Health Center Reports Data Security Incident

On or around December 15, 2025, Clarinda learned that certain data within its network may have been accessed without authorization.


Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures

Environmental cleaning is crucial in preventing HAIs, but when the responsibility falls to those outside of EVS teams, problems arise. 


Ground Broken on the Southern Nevada Forensic Facility

Construction on the new secure forensic psychiatric hospital is expected to be completed in 2029.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.