Q: I have a surgery suite that had a hole punched into the wall by the door knob. Is there anything in LSC that states " if a hole is made in a surgery wall the drywall needs to be replaced from stud to stud", not just repair the hole?

A: No… The LSC does not concern itself with the way the walls are constructed. When it comes to walls, the LSC only concerns itself with identifying which walls must be smoke resistant, fire-rated, or smoke rated. The UL listings for the walls will determine how the wall is constructed.

Now, if the wall with the door knob hole is only required to be smoke resistant, then you can seal the hole with any type of patch that makes the wall resistant to the passage of smoke. But if the wall is fire-rated, or is required to be a 1-hour rated smoke barrier, then you must excise the hole from stud to stud, insert a new piece of gypsum board, and screw, tape and apply joint compound in accordance with the UL listing for that wall.

I’m sure your Infection Control practitioner would have a lot to say about a hole in a wall in surgery.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



October 31, 2018



Recent Posts

Why Healthcare Facilities Management Is Critical to Patient Safety 

Hospitals and other healthcare facilities rely on much more than doctors and nurses to keep patients safe.


Brookdale Senior Living Announces Acquisition of the Brookdale Galleria Community

The 244-unit independent living and assisted living community is located directly adjacent to The Galleria shopping and entertainment complex.


Erlanger Health System Falls Victim to Data Breach

Erlanger has no evidence of any improper use of the information because of this incident.


Technological Readiness: The Missing Construction Milestone

A new building can be complete by most measures but still not be technologically or operationally ready.


From Cooling Towers to Cost Savings: Hospital Seizes Power-Saving Opportunity

Case study: Arkansas hospital increases energy efficiency by diagnosing cooling tower issues and treating its entire mechanical system.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.