Regulations, Codes & Standards Q&A: Missing ceiling tiles

Brad Keyes discusses regulations for missing ceiling tiles

By Brad Keyes / Special to Healthcare Facilities Today


Q: Do missing ceiling tiles in a suspend create a Life Safety Code deficiency in an existing business occupancy? Should section 4.6.12.2 of the 2012 Life Safety Code apply to require the maintenance of broken or missing ceiling tiles in a business occupancy?

A: The complete membrane that the ceiling forms is required if sprinklers or smoke (or heat) detectors are installed in the room or area served by the ceiling. The ceiling acts to trap the heat and smoke and allows the sprinklers or detectors to operate.  

Otherwise, if a ceiling tile is missing, or has excessive gaps around penetrations, or the ceiling tiles have holes, then heat and smoke can continue up into the interstitial space above and the operation of the sprinklers and/or detectors would be delayed, thus causing an impairment.

If there are no sprinklers or smoke (or heat) detectors in the room or area, then there may not be any Life Safety Code reason for the ceiling system, unless it serves as part of the fire-rated floor/ceiling system, such as UL-G227 or UL-G235. Section 4.6.12.2 would not apply if the ceiling is not serving a purpose of life safety.

Now, the suspended grid and tile ceiling may serve an Infection Control purpose, and you would have to maintain it for that reason, but that is not a Life Safety Code purpose.

Yes… this would apply to business occupancies. It is not dependent on any particular occupancy.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 



January 10, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

EVS Leadership Culture Critical in Preventing Hospital-Acquired Sepsis

Cleaning is an essential yet complex component for the prevention of HAI-induced sepsis.


Man Dies by Suicide in Emergency Department Waiting Room at Kansas Hospital

No staff or patients were harmed, and the man was alone in the waiting area when he shot himself.


McCarthy Completes North Tower at Scripps Memorial Hospital La Jolla

The new $664 million, eight-floor acute care tower expands access to advanced medical services for the Southern California region.


Wesley Rehabilitation Center Specializes in Patients from Design to Care

Barge knew that patients were at the core of the design process.


Casa Colina Center for Disorders of Consciousness Officially Opens

New program addresses critical need for patients with severe brain injuries.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.