Regulations, Codes & Standards Q&A: More On Power Strips

Brad Keyes discusses regulations related to power strips

By Brad Keyes / Special to Healthcare Facilities Today


Q: I need some insight on a debate within our organization. Our life-safety team member has made the statement that we can use a power strip within the operating room, in the patient care vicinity, as long as it is attached to a rack/cart/table etc. (obviously meeting the UL1363a standard is a stated requirement as well).

To me, this is a clear misinterpretation of the standard, as the medical equipment must be rack/cart/table mounted, and then the power strip, can be used with that equipment as long as its mounted to the same assembly.

The life safety employee is essentially proposing that we can mount the power strip permanently to a stainless-steel surgical table, and anything that is a medical device can be connected to the strip, at will, essentially making it a table mounted power extender. I do not believe this to be within the standard, based on my interpretation the standards provided to us.

Am I misinterpreting this? Or is this acceptable practice to attach a power strip, to essentially a piece of furniture, and okay it for use in an OR?

A: As I read NFPA 99-2012, section 10.2.3.6, power strips used within the patient care vicinity must only be used on movable equipment assemblies that are rack-mounted, table-mounted, pedestal-mounted, or cart-mounted. So, the idea of installing a UL 1363A power strip on a table is permitted within an operating room, provided the patient care related electrical equipment plugged into the power strip is considered movable. The question raised is, if it is movable, then why is it mounted on a table? The intent appears to me that the movable equipment is designed to be table-mounted (not just placed on a table) and may have a UL 1363A power strip, but you cannot have a UL 1363A power strip mounted to a movable table that is just waiting for general use. The UL 1363A power strip must serve a piece of movable patient care related electrical equipment.

I would agree with you that the practice of attaching a 1363A power strip to a movable table for use by any equipment does not meet the intent of CMS K-Tag 920 or NFPA 99-2012, 10.2.3.6.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



September 23, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

Grounding Healthcare Spaces in Hospitality Principles

Thoughtful design can establish the calm of a spa and the restorative feeling of a resort in healthcare spaces, bringing benefits for patients and care providers.


UC Davis Health Selects Rudolph and Sletten for Central Utility Plant Expansion

Work is already underway with substantial completion anticipated in the fall of 2027.


Cape Cod Healthcare Opens Upper 2 Floors of Edwin Barbey Patient Care Pavilion

The first two floors opened for patients in May 2025 and house the Davenport-Mugar Cancer Center.


Building Sustainable Healthcare for an Aging Population

Traditional responses — building more primary and secondary care facilities — are no longer sustainable.


Froedtert ThedaCare Announces Opening of ThedaCare Medical Center-Oshkosh

The organization broke ground on the health campus in March 2024.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.