Regulations, Codes & Standards Q&A: Portable fire extinguishers

Brad Keyes discusses regulations for portable fire extinguishers

By Brad Keyes / Special to Healthcare Facilities Today


Q: In regards to portable fire extinguishers, I have a fully sprinkled building but my room that my hot water heaters are in are on the outside of the building. My furthest hot water room is more than 75 feet from the closet fire extinguisher. I looked in the Life Safety Code and have not found any reference on this. Do I need to place a fire extinguisher in this room?

A: Yes, you do… Section 9.7.4.1 of the 2012 LSC requires compliance with NFPA 10. According to chapter 6 of NFPA 10-2010, the installation of portable fire extinguishers is based on the classification of the extinguisher, the capacity of the extinguisher, and the level of hazard the extinguisher is expected to address.

For Class A extinguishers, the maximum travel distance to an extinguisher is 75 feet. For Class B extinguishers, the maximum travel distance is either 30 feet or 50 feet, depending on the capacity of the extinguisher and the expected level of hazard. For Class C extinguishers, the fire is started by electrical current, but the material that burns is either a Class A material or a Class B material, so you space the extinguishers on the class A or Class B requirements. For a Class K extinguisher, the maximum travel distance is 30 feet.  

You need to install an extinguisher to be within the maximum travel distance limits.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.

 

 



October 24, 2018


Topic Area: Regulations, Codes & Standards


Recent Posts

Mattresses Require Strict Care to Prevent Spread of Infections

Poor cleaning and disinfection techniques contribute to the persistent contamination of patient mattresses.


Gardner Health Services Opens Alum Rock Health Center

The 10,080-square-foot facility provides essential medical, dental, mental and chiropractic services to the Mayfair and East San José neighborhoods.


The Children's Center of Hamden Reports Data Security Incident

The incident was detected on December 28, 2024.


Designing for Senior Care Communities Means Designing for Everyone

No spaces can be designed for just one person, designers need to think about everyone who will occupy the space.


Harlem Hospital Legionnaires' Outbreak Highlights Cooling Tower Risks

Seven deaths linked to the cooling towers underscore the need for stricter water system monitoring and preventive maintenance in healthcare settings.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.