Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Replacing Old Smoke Detectors

Brad Keyes discusses regulations on replacing old smoke detectors

By Brad Keyes / Special to Healthcare Facilities Today


Q: I have been told that if we have smoke detectors that are more than 15 years old, then they are required to be replaced with new ones. Is there a code for this? I have asked our vendor to test our smoke detectors for sensitivity, and they said we need to replace all of them. We do have an older panel where they would have to go point by point to do this, rather than measure the sensitivity at the panel.

A: Whether addressable or conventional, there’s no code that mandates the replacement of a smoke detector so long as it’s sensing smoke per the manufacturer’s listed sensitivity range.  Each detector’s sensitivity must be verified via one of the methods outlined in NFPA 72 (2010) Table 14.4.2.2.14(g)(1). 

I’d advise the owner to have the testing company describe their sensitivity test methods and compare it with the allowed methods.  I can tell you from experience that some vendors view a ‘chamber entry’ test as a sensitivity test.  A chamber entry test just tests the ability of smoke to enter the sensing chamber and activate the detector, not the sensitivity of the detector to the presence of smoke.  Just spraying smoke at a detector is not a sensitivity test.

There is a rule of thumb that it’s best to replace detectors after 15 years, but its purpose is to keep from getting nickel & dimed by dying detectors, much like getting nickel & dimed by a 15-year-old car.  It’s a good idea to get in front of device replacement circuit by circuit in order to control costs and avoid paying for emergency overtime service calls.

This answer was provided by Gene Rowe, Director of Business Development at Affiliated Fire Systems, Inc.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



October 14, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

Casa Colina Center for Disorders of Consciousness Officially Opens

New program addresses critical need for patients with severe brain injuries.


Legionella Detected at Michigan Health Facility

Case follows a similar finding of Legionnaires’ disease in a former patient.


Crystal Spring Tower Opens at Carilion Roanoke Memorial Hospital

The new cardiovascular institute improves access and care across the region.


Hospital Evacuation Highlights Importance of Emergency Preparedness

Berger Hospital was evacuated after smoke was discovered in the basement.


Building a Culture of Infection Prevention

Investing in infection prevention can benefit healthcare organizations and patient outcomes.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

 
 
 
 

Healthcare Facilities Today membership includes free email newsletters from our facility-industry brands.

Facebook   Twitter   LinkedIn   Posts

Copyright © 2023 TradePress. All rights reserved.