Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Start/Stop Times For Generator Load Test

Brad Keyes discusses regulations for generator load tests

By Brad Keyes / Special to Healthcare Facilities Today


Q: Is there a standard, that says we need to write the start and stop time on our monthly generator load test for 30 minutes?

A: In so many words there is. I agree that you won’t find a specific standard that says you must record the start and stop times of each test, but section 8.4.2 of NFPA 110-2010 says Diesel generator sets in service shall be exercised at least once monthly, for a minimum of 30 minutes, using one of the following methods:

(1) Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer

(2) Under operating temperature conditions and at not less than 30 percent of the EPS nameplate kW rating

If you do not record the start and stop times then how do you prove to a surveyor that you tested the generator for 30-minutes?

It is reasonable and logical for a surveyor to expect you to record the start and stop times to ensure you tested the generator for 30 minutes.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



September 30, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

The OR HVAC Puzzle: Why Individual Systems Are on the Rise

Extra penetrations, tight clearances and strict humidity needs—design experts explain what it really takes to plan dedicated units for each operating room.


Sutter Health Announces Plans for New Santa Clara Medical Center

Sutter projects the medical center will open in late 2031.


Sanford Health Receives $300M Gift for Black Hills Medical Center Campus

Construction is scheduled to begin in 2027 with completion expected by 2030.


Wanted: Scientific Standard for Hospital Cleaning

No accepted criteria exist for defining a surface as clean using microbiologic methods.


NLCS Strengthens Safety and Compliance with Comprehensive Electrical Program

Case study: A renewed partnership with Siemens helps the senior living provider meet NFPA 70B standards, reduce risk, and enhance reliability across its communities.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.