Focus: Fire-Life Safety / Column

Regulations, Codes & Standards Q&A: Start/Stop Times For Generator Load Test

Brad Keyes discusses regulations for generator load tests

By Brad Keyes / Special to Healthcare Facilities Today


Q: Is there a standard, that says we need to write the start and stop time on our monthly generator load test for 30 minutes?

A: In so many words there is. I agree that you won’t find a specific standard that says you must record the start and stop times of each test, but section 8.4.2 of NFPA 110-2010 says Diesel generator sets in service shall be exercised at least once monthly, for a minimum of 30 minutes, using one of the following methods:

(1) Loading that maintains the minimum exhaust gas temperatures as recommended by the manufacturer

(2) Under operating temperature conditions and at not less than 30 percent of the EPS nameplate kW rating

If you do not record the start and stop times then how do you prove to a surveyor that you tested the generator for 30-minutes?

It is reasonable and logical for a surveyor to expect you to record the start and stop times to ensure you tested the generator for 30 minutes.

Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



September 30, 2020


Topic Area: Regulations, Codes & Standards


Recent Posts

Avoiding Mistakes in Healthcare Site Selection

Actionable strategies for healthcare systems and medical groups navigating today’s constrained real estate market.


Can Rural Hospitals Be Saved?

More than 700 rural hospitals nationwide face the risk of closure. A new report highlights solutions that could improve long-term sustainability.


Ascension Saint Thomas Breaks Ground on Hospital and Health Campus in Tennessee

The new hospital will open with 44 inpatient beds and will be designed to expand to 132 beds as community needs grow.


The Hidden Risks of QAC Disinfectants in Healthcare Facilities

Quaternary ammonium compounds are a popular disinfectant choice, but they may be causing more harm than good. A review outlines the problems with QACs and offers a solution.


Sprinkler Compliance: Navigating Code Mandates, Renovation Triggers and Patient Safety

As CMS deadlines approach and renovation projects accelerate, healthcare facility managers must understand how NFPA 101, state fire codes and sprinkler design strategies intersect.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.