Test, inspect, maintain: Fire suppression system priorities

If the facility or its mission changes, facility managers must be able to recognize and understand how those changes might cause a water-based fire suppression system to fail


As a facility or its mission changes, it is possible to recognize basic types of changes that might cause a water-based fire suppression system to fail routine testing, even if the system was properly designed to suit the original facility and is well maintained. Changes to facilities that alter the occupancy group, hazard classification, building footprint or building height are cause for a complete re-evaluation, according to an article from Building Operating Management on the FacilitiesNet website.

Some examples include:

Because standpipe systems generally place the highest fire water demand on a facility, changes that affect a new standpipe system or affect an existing standpipe system may render an existing fire water supply inadequate. Keep in mind that automatic standpipes place particularly high demands on water supplies, and that partially-sprinklered buildings have higher standpipe flow demands than fully-sprinklered buildings.

Vertical additions to a building without a standpipe system may require that a standpipe system be added.

Vertical additions to a building with an existing standpipe system in which a story or stories are added increases demand pressure.

Horizontal additions to a building with an existing standpipe system in which an exit stair or stairs are added increases demand flow.

Horizontal additions to a building with an existing standpipe system in which a horizontal exit or exits are added increases demand flow.

Helipads added to rooftops have unique fire suppression requirements.

Fire sprinkler system demands will generally be lower than that of standpipe systems. However, there are instances where changing fire sprinkler demands also create hydraulic demands that exceed supply.

Fully sprinklering a partially sprinklered facility may create a new hydraulically remote area.

Changing the use of a space to a higher hazard will increase the required flow density, and may require a new fire sprinkler layout.  An example of this is changing office area to storage.

Adding interior walls in a remote area of the building may require additional fire sprinklers.

The effects of aging of on water-based fire suppression systems include corrosion, scale, and sediment. These problems are normal because of water coming in contact with metallic components.  Increased friction loss through metal piping and oxidation of wetted sprinkler head components mean that fire suppression systems and components have a finite life span.

Read the article.

 



August 21, 2018


Topic Area: Safety


Recent Posts

Wesley Rehabilitation Center Specializes in Patients from Design to Care

Barge knew that patients were at the core of the design process.


Casa Colina Center for Disorders of Consciousness Officially Opens

New program addresses critical need for patients with severe brain injuries.


Legionella Detected at Michigan Health Facility

Case follows a similar finding of Legionnaires’ disease in a former patient.


Crystal Spring Tower Opens at Carilion Roanoke Memorial Hospital

The new cardiovascular institute improves access and care across the region.


Hospital Evacuation Highlights Importance of Emergency Preparedness

Berger Hospital was evacuated after smoke was discovered in the basement.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.