Backflow preventers Q&A

In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about backflow preventers


In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers. 

Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?

A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.

Read the full answer.

 

 



August 26, 2014


Topic Area: Maintenance and Operations


Recent Posts

Mature Dry Surface Biofilm Presents a Problem for Candida Auris

Multiple methods are described in the literature, but no consensus has been reached for disinfection efficacy tests against biofilms.


Sutter Health's Arden Care Center Officially Opens

With an adaptive reuse of an underutilized office building, the 70,000 square-foot facility was renovated to meet current healthcare standards.


Insight Hospital and Medical Center Falls to Data Breach

The investigation determined that an unauthorized individual accessed the network between August 22, 2025, and September 11, 2025.


The High Cost of Healthcare Violence

As workplace violence increases, healthcare facilities face mounting financial and operational disruptions- prompting legislative action.


EVS Teams Can Improve Patient Experience in Emergency Departments

A report confirmed that cleanliness of the ED was the third most impactful element on patient experience surveys.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.