In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
Creating Healthcare Campus Master Plans That Allow Movement and Respite
Aspirus Health Celebrates Opening of Chippewa Falls Hospital and Clinic
AdventHealth to Open Aurora Highlands Medical Campus
The Future of Healthcare Facility Construction Projects
Arnprior Regional Health Upgrades Building Controls to Improve IEQ