In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
How Curated Art Elevates Senior Care Spaces
The CDC's Guide to Hand Hygiene in Healthcare
Dana-Farber, BIDMC Launch Construction of Dedicated Adult Cancer Hospital
5 Components of an Integrated Safety Culture in Healthcare
NYC Opens Therapeutic Housing Unit for Medically Vulnerable Detainees