In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
Rethinking Strategies for Construction Success
From Touchless to Total Performance: Healthcare Restroom Design Redefined
New York State Approves $53M Construction Program at Niagara Falls Memorial Medical Center
How Health Systems Are Rethinking Facilities Amid Margin Pressure
Ground Broken on New Medical Office Building in Scottsdale, AZ