In a recent Q&A on the FacilityCare website, consultant Brad Keyes answered a question about testing requirements for backflow preventers.
Q: Many authorities having jurisdiction are requiring reduced pressure zone backflow devices on sprinkler systems. Is there a testing requirement for these devices?
A: Yes, backflow preventers, both double-check and RPZ types, must be tested on an annual basis when connected to sprinkler systems. NFPA 25 requires all backflow preventers installed in fire protection system piping to be tested annually at the designed flow rate of the fire protection system.
Cleanliness in Hospitals: Clinical Priority and Community Perception
Dana-Farber Receives $50M Gift for Planned Cancer Hospital
Clarinda Regional Health Center Reports Data Security Incident
Gaps in Nurses' Environmental Cleaning Knowledge Grow Amid Rising EVS Pressures
Ground Broken on the Southern Nevada Forensic Facility