Can Hospitals Use Door Wedges?

Brad Keyes explains the requirements for holding doors open in hospitals


Question: Are there any particular requirements that prohibit use of wooden door wedges in a hospital facility?  

 

Answer from Brad Keyes: Yes. Section 19.3.6.3.10 of the 2012 Life Safety Code says corridor doors shall not be held open by devices other than those that release when the door is pushed or pulled. Therefore, a wedge holding the corridor door open would never be permitted because it would not release if the door was pushed or pulled. 

 

However, door wedges would be permitted on doors that were not required to self-close (such as a hazardous room), corridor doors, smoke barrier doors, or fire-rated doors. So, doors inside a suite-of-rooms may be able to be wedged open as long as they were not required to self-close, a corridor door, a smoke barrier door, or a fire-rated door. But this is not a desirable thing to allow, even in areas where it is permitted as staff will not fully understand where they can and cannot wedge doors open. 


Brad Keyes, CHSP, is the owner of KEYES Life Safety Compliance, and his expertise is in the management of the Life Safety Program, including the Environment of Care and Emergency Management programs.



December 23, 2020


Topic Area: Safety


Recent Posts

Building Sustainable Healthcare for an Aging Population

Traditional responses — building more primary and secondary care facilities — are no longer sustainable.


Froedtert ThedaCare Announces Opening of ThedaCare Medical Center-Oshkosh

The organization broke ground on the health campus in March 2024.


Touchmark Acquires The Hacienda at Georgetown Senior Living Facility

The facility will now be known as Touchmark at Georgetown.


Contaminants Under Foot: A Closer Look at Patient Room Floors

So-called dust bunnies on hospital room floors contain dust particles that turn out to be the major source of the bacteria humans breathe.


Power Outages Largely Driven by Extreme Weather Events

Almost half of power outages in the United States were caused by extreme weather events.


 
 


FREE Newsletter Signup Form

News & Updates | Webcast Alerts
Building Technologies | & More!

 
 
 


All fields are required. This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.